ELC500 Control unit
87
■
Basic setup
Set items related to logging data.
Item
Description
(a)
File name *1
Set name for logging file (csv).
<Set range>:32-letter or less
(b)
Logging trigger No.
Set trigger to use for data logging.
It logs data to file at setting trigger.
(c)
Saved file number
Set number of saved logging file in the folder.
<Initial>100
<Set range> 1 to 100
(d)
Timing for create new file
Set timing for creating a logging file.
・
Record number
At reach the setting record, it creates new logging file.
<Set range>: 1 to 100000
・
Trigger
At setting trigger is occurs, it creates new logging file.
*1 It can’t use the below letters.
letter
name
letter
Name
¥
Yen
*
Asterisk
/
Slash
?
Question mark
\
Backslash
‘
Double quotation
:
Colon
<
Inequality sign
;
Semi-colon
>
Inequality sign
.
dot
|
pipe
Half-width space
(only the beginning)
Note
- If the number of registered devices to log is increased or if there is a wireless device in
the system, it is difficult to collect in short cycle and it may cause missing data.
- Be sure to set a cycle to record collected data longer than a cycle to collect data. If not, it
may cause missing data.
- When the number of record exceeds 65536 (including header), it can’t open the file by
Excel 2003 or earlier version.
- Be sure to set logging trigger doesn’t overlap new file creating timing. Of not, it may not
record correct data nor send mail nor upload files.
- If saved file number is changed to a number smaller than the previous, it deletes files
from the older file at the next time when it creates logging file.
(a)
(b)
(c)
(d)