ELC500 Control unit
14
(6) DIN hook
Use to install it on DIN rail. Installation Removal
(7) LAN port
Use for connecting to Ethernet LAN. It can be connected programming tool.
MAC address is printed on the side of ELC500.
It supports the Ethernet interface of 100BASE-TX and 10BASE-T and switches automatic
by auto
negotiation function.
・
Status of LED and working
LED
Working
LINK
Lights when connecting the devices via Ethernet
ACT
Flashes when transmitting or receiving command or response between the
connecting devices
(8) USB port
Connect USB cable
Use it to connect PC when using ‘Configurator EL500’ and ‘FPWIN Pro7’.
Use MiniB type for ELC500.
(9) Unit connector
Connect I/O unit or high-function unit. End unit is connected when shipped.
(10) Dip switch
Do not change the setting. It default set to OFF all.
Pin No.
Signal
Direction
Remarks
1
TX+
Output
Transmitting data (+)
2
TX-
Output
Transmitting data (-)
3
RX+
Input
Receiving data (+)
4
N.C.
---
No connection
5
N.C.
---
No connection
6
RX-
Input
Receiving data (-)
7
N.C.
---
No connection
8
N.C.
---
No connection
LINK
ACT
Содержание ELC500
Страница 1: ......
Страница 18: ...ELC500 Control unit 10 Point Using FPWIN PRO7 you can check the cunsumption current ...
Страница 206: ...ELC500 Control unit 198 Dimensions and Others Chapter 12 Dimensions 12 1 Unit mm ...
Страница 207: ...ELC500 Control unit Revision History Issue Date Manual no Content of revision September 2018 WUME ELC5 01 First edition ...
Страница 208: ... ...