ELC500 Control unit
187
Error Code
10.4
Code
Name
Operation
Error contents and steps to take
0
Unit warning
Stop
Unexpected setting error.
Please contact us.
1
CPU hardware error 1
Stop
There may be a hardware problem. Please contact your
dealer.
2
CPU hardware error 2
Stop
3
I/O bus power supply
error (including "no end
cover")
Stop
Error in the I/O bus part is probable, such that the end
unit has not been attached. Double-check the
attachment status of units. This error also occurs when
an expansion cable is removed during operation.
4
Unit attachment limit
exceeded
Stop
It is probable that the unit attachment limit has been
exceeded. Double-check the configuration.
5
Project data error
Stop
Turns on when there is an error in project data.
6
Expansion unit power
supply synchronization
error
Stop
Turns on when there is an error in the expansion block
side such that the power to the expansion unit is not on
or the expansion cable is not connected correctly when
the power turns on. The wait time until the power turns
on can be set in the I/O map configuration dialog box.
18
ELC configuration data
error
Stop
Setup data for ELC500 may be broken.
Start Configurator EL500 and create new setup.
19
ELC ladder
authentication error
Stop
It may be deleted ELC dedicated ladder.
Download the project file from our website and transmit
it to ELC500. (ELC500SystemLadder_v***.pce)