ELC500 Control unit
5
<Analog input and output units>
Product name
Specifications
Number of
channels
Model No.
FP7 analog input unit
(high-speed and
multi-channel type)
Voltage / current, conversion rate:
25 μs/channel, resolution: max. 16 bits,
accuracy: ±0.1 % F.S. or less (at 25
℃
) *1
8 channels
AFP7AD8
FP7 analog input unit
(High-speed and
high-accuracy type)
Voltage / current, conversion rate:
25 μs/channel, resolution: max. 16 bits,
accuracy: ±0.05 % F.S. or less (at 25
℃
) /
insulation between channels
4 channels
AFP7AD4H
FP7 analog output unit
(High-speed and
high-accuracy type)
Voltage / current, conversion rate:
25 μs/channel, resolution: max. 16 bits,
accuracy: ±0.05 % F.S. or less (at 25
℃
) /
insulation between channels
4 channels
AFP7DA4H
*1 The digital conversion value corresponding to the analog input of about 2 V is stored in the input relay area
(WX) to the channel that is not connected when voltage range setup.
<Temperature input units>
Product name
Specifications
Model No.
Thermocouple multiple
analog input unit
8ch
・
[Thermocouple(resolution: 0.1
℃
)]
K/J/T/N/R/S/B/E/PL
Ⅱ
/WRe5-26
・
[Voltage/Current] Resolution: max. 16 bits
AFP7TC8
Resistance temperature
detector input unit
8ch
・
[Resistance temperature detector(resolution: 0.1
℃
)]
Pt100/JPt100/Pt1000
AFP7RTD8
<Multi input/output units>
Number of
points
Connection
method
Specifications
Model No.
Input: 16 points
Output: 16
points
MIL
connector
Input: Total 16 points
•DC input: Max. 16 points
•High-speed counter: Max. 4 channels
(1 channel: 4 points)
•Interrupt input: Max. 8 points Output: Total 16 points
•Transistor output: Max. 16 points
•Pulse output: Max. 4 channels (1 channel: 2 points) *1
•PWM output: Max. 4 channels (1 channel: 1 points)
•Comparison output: Max. 8 points
AFP7MXY32
DWD
*1 Trapezoidal control with acceleration / deceleration not yet supported.
Note) FP7 multi input/output unit positioning type (Model No. AFP7MXY32DWDH) is not supported.
<High-speed counter units>
Specifications
Model No.
Input time
constant
Number of
counters
Counter type
Input type
Selection
type
2 channels
Liner counter
/ring counter
Individual input: 1 multiple, 2-multiple
Direction discrimination input:
1 multiple, 2-multiple
2-phase input: 1 multiple, 2-multiple,
4-multiple
AFP7HSC2T
4 channels
AFP7HSC4T