Installation and Cabling
Chapter 3
Installation
3.1
Install Space
3.1.1
■
Panel installing space
・
Leave at least 50 mm of space between the wiring ducts of the unit
and other devices to allow heat radiation and the unit replacement.
■
For heat discharge
・
Do not install the unit as shown below.
It is not enough to h
eat dissipation and it will cause internal abnormal heat generation.
・
Do not install on the top of the devices with high heat generation such as heater, transformer,
high-capacity register and so on.
・
Keep at least 100mm of space between devices to avoid adverse effects from noise or heat when
installing a device or panel door to the front of the unit.
100mm or more
Panel door
ELC
Other
device
・
Leave at least 170mm of space from the front surface of the unit in order to allow room for wiring.
170mm or more
ELC
Other device
50mm or more
ELC
50mm or more
Vertical Horizontal Upside-down