![Panasonic ELC500 Скачать руководство пользователя страница 71](http://html.mh-extra.com/html/panasonic/elc500/elc500_user-manual_262672071.webp)
ELC500 Control unit
63
■
Usage: Program control(PLC)
Item
Description
(a)
Usage
Set usage for serial communication.
<Initial> Data collection(ELC)
<Set range> Data collection(ELC) / Program control(PLC)
(b)
Protocol *3
Set communication protocol.
<Initial> MEWTOCOL-COM master/slave
<Set range>
MEWTOCOL-COM master/slave
MEWTOCOL7-COM slave
MODBUS RTU master/slave
General communication *1
PLC link *2
(c)
Unit No. *4
Set unit number of ELC500.
<Initial> 1
<Set range>
MEWTOCOL-COM master/slave:
1 to 99
MEWTOCOL7-COM slave:
1 to 999
MODBUS RTU master/slave:
1 to 247
General communication:
1 to 999
(d)
Baud rate
Set baud rate.
<Initial> 19200bps
<Set range> 300/ 600 / 1200 / 2400 / 4800 / 9600 / 19200 /
38400 / 57600 / 115200 / 230400
(e)
Data length *5
Set data length.
<Initial> 8bit
<Set range> 7bit / 8bit
(f)
Parity
Set parity.
<Initial> Odd
<Set range> None / Odd / Even
(g)
Stop bit
Set stop bit.
<Initial> 1bit
<Set range> 1bit / 2bit
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
(j)
(k)