ELC500 Control unit
184
■
Condition
Cause
Action to take
Cannot send a mail
Ethernet cable is disconnected.
Connect Ethernet cable correctly.
Setting for SMTP server is not
correct.
Set IP address of SMTP server correctly.
When SMTP server is specified with a name,
check if IP address setting for DNS server is
correct.
Destination mail address is not set
correctly.
Set the destination mail address correctly at user
registration window.
Source mail address is not
corrected.
Depending on mail servers, the source mail
address may be checked.
Set the source mail address correctly at ‘Mail
setup’.
Destination is not selected.
Check if the destination is selected or not.
Cannot send a mail by
creating a file
Sending setting is not correct.
Set ‘Mail sending’ and ‘Destination’ correctly at
setup window.
■
Low-level communication
Condition
Cause
Action to take
Although a command
has been transmitted,
no response is received.
Your machine is not wired with the
other machine correctly.
In case of RS232C
Connect SD/RD lines of your machine to
RD/SD lines of the other machine respectively.
In case of RS-485
Connect the transmission cable between the
(
+
) transmission terminals and between the
(
-
) transmission terminals of each device.
Also connect the terminal station correctly.
Check the transmission cable specs is within
the specifications.
*Use one type of transmission cable in the same
link. Do not mix more than one type.
Communication conditions of your
machine and the other machine
are not matched.
Check the communication conditions of ‘COM’
at Basic configuration.
The same unit number may be used
for destination devices.
Check the unit number settings of destination
devices.
Wait time for sending or timeout is
too short.
Make wait time for sending or timeout longer.
Connect our Temperature
Controller and the terminal register.
Not necessary to connect the terminal register.
Cannot collect data of KW2G. The unit number setting of ELC may
be wrong.
One unit number is allocated to one base unit
even if an expansion unit is connected.
Designate DT00500 for collecting
with using our wireless unit.
When using the wireless unit, DT00500 is used
for abnormal flag. Set DT00520.
Remote I/O unit doesn’t work
according to setup conditions
Setup data is not transmitted to
remote I/O unit.
Set ELC500 to RUN mode.
Remote I/O unit is set to forced
output mode.
Check that dip switch No.9 of remote I/O unit is
set to OFF