Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
86
than for fire alarm, i.e. pre-warning will be activated before the
fire alarm from the same alarm point.
3.
heavy smoke alarm
will be activated at a higher level (bigger
offset) than for fire alarm, i.e. heavy smoke alarm will be
activated later than the fire alarm from the same alarm point.
The pre-warning offset and the heavy smoke alarm level can, for the
whole system, be set in Win512 version 2.7.x, see chapter "Alarm
algorithms", page 137.
The fire alarm offset can, for the whole system, be set in Win512
version 2.7.x, see chapter "Alarm algorithms", page 137.
NOTE!
This is not a normal action and a special password is required.
"Pre-warning", "Fire Alarm" and "Heavy Smoke Alarm" can activate
programmable outputs respectively, see chapter "Control expression",
page 71. See also EBL512 G3 United version 2.7.x Operating
Instructions MEW01473.
16.4.1
Alarm algorithm / Alternative alarm algorithm
In order to reduce the nuisance alarms
83
and ensure that the real fire
alarms will be activated, six different alarm algorithms are available.
See Figure 18., page 87. They are based on:
Normal (N), High (H) or Low (L) sensitivity
Normal (15 sec.) or slow (35 sec.) detection time
Normal sensitivity
(Default) Fire alarm offset is
3.0 %
smoke
obscuration per meter.
High sensitivity
Fire alarm offset is
2.4 %
smoke obscuration per
meter, i.e. less than for normal sensitivity. Can be used when an
"early" fire alarm is wanted.
Low sensitivity
Fire alarm offset is
3.6 %
smoke obscuration per
meter, i.e. more than for normal sensitivity. Can be used to reduce
nuisance alarms
83
.
Normal detection time - 15 sec.
(Default) There will always be min.
15 seconds alarm delay
84
. This is a "normal filter" to reduce nuisance
alarms.
Slow detection time - 35 sec.
. There will always be min. 35 seconds
alarm delay
. This is an "extra filter" to reduce nuisance alarms
83
.
Each analog smoke detector can have two alarm algorithms
programmed (via Win512 version 2.7.x). One
Regular alarm
algorithm
that is normally used (
N-15
is default) and one
Alternative
alarm algorithm
that is turned on/off via a time channel (internal or
external). E.g. normal sensitivity can be used during night-time and
83
So called false / unnecessary alarms.
84
After the fire alarm level is reached / passed, it will take min. 15 alt. 35
seconds until fire alarm will be activated in the c.i.e.