Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
139
21.6.3
Smoke detectors' (3304, 4301, 3316 and 4300)
properties
Detector
:
3304 / 4301(OPT)
3316 / 4300 SMOKE (AMD), i.e. the smoke detector part
when decision algorithm is not selected.
Logical name
: L-15 Low sens. 15s, L-35 Low sens. 35s, N-15
Normal sens. 15s, N-35 Normal sens. 35s, H-15 High sens. 15s and H-
35 High sens. 35s.
Short name
: L-15- L35, N-15, N-35, H-15 and H-35.
Algorithm parameters
: Default values, see table:
3304 / 4301
(OPT)
3316 / 4300 SMOKE
(AMD)
L-15
L-35
N-15
N-35
H-15
H-35
L-15
L-35
N-15
N-35
H-15
H-35
Offset,
Smouldering
18
18
15
15
12
12
18
18
15
15
12
12
Offset,
Pre-warning
26
26
22
22
18
18
26
26
22
22
18
18
Offset,
Fire alarm
36
36
30
30
24
24
36
36
30
30
24
24
Level,
Heavy alarm
150
150
150
150
150
150
120
120
120
120
120
120
Step
value
A
6
2
5
2
4
2
12
4
10
4
8
4
NOTE! If any of these values are changed, it might be a violation
to the EN54-2 standard.
A
The "Step value" is used in the alarm algorithm.
21.6.4
Multi detectors' (3316 and 4300 + decision algorithm)
properties
Detector
:
3316 / 4300 SMOKE (AMD), i.e. the 3316 detector when
decision algorithm is selected.
Logical name
: Decision algorithm
Short name
: Dec (Shown in menu H4/U5.
Algorithm parameters
: Default values, see table:
3316 / 4300
SMOKE
(AMD)
Offset,
Smoke Pre-
warning
50
Offset,
Smoke alarm
58
Level,
Heat Pre-warning
50
Level,
Heat alarm
58