Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
68
13.2
Logic
(•) Normally open / low
Normally open relay contact or normally
low voltage output.
60
( ) Normally closed / high
Normally closed relay contact or
normally high voltage output (24V DC).
61
13.3
Supervised / Not supervised
A voltage output is supervised (default). By unmarking the
"Supervised" checkbox the voltage output will be not supervised.
A normally high output cannot be supervised.
13.4
Time Activation Output
Each output uses an "Time Activation Output", which controls the
output's activation. The following are available:
No. 1 is default Steady / Continuous. No. 2 is default intermittent
0.8/0.8s. No. 3-8 can be built up with type and time.
Types
:
0.
Steady (continuous)
1.
Intermittent
2.
Pulse
3.
Steady, Delayed Activation
4.
Intermittent, Delayed Activation
5.
Pulse, Delayed Activation
6.
Steady, Delayed De-Activation
60
The logic is set in the Win512 version 2.7.x dialog box "Voltage / Relayed
Output".
61
The logic is set in the Win512 version 2.7.x dialog box "Voltage / Relayed
Output".
NOTE!
A normally high output can not be supervised and it will
be low for a few seconds during restart of the c.i.e.