Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
34
Each input (0-15) has to be programmed
via Win512 version 2.7.x
regarding:
Zone (control) no. (0-15)
6.5
Inputs and outputs expansion board 4583
Cannot be used for EBL512 G3 United version 2.7.x.
6.6
External FBP / DU interface board 1587
One 1587 board has to be programmed when Display Units type 1728,
1735, 1736, 1826 and 1828 shall be connected to an
EBL512 G3
control unit with S/W United version 2.7.x, i.e. connected in a mixed
system. No physical board shall be mounted – the Display Units are
connected directly in the
EBL512 G3
control unit (RS585).
The "board" has to be programmed
(via Win512 version 2.7.x) in
spite of that no physical board is used, regarding:
Address (one exp. board address 0-5)
Name (Default is
FBP/DU 1587
, which is normally not changed)
This board is programmed for connection of Ext. FBPs 1826 / 1828,
Presentation units 1728 and Alert annunciation units 1735 / 1736 to
EBL512 G3 United version 2.7.x. They shall be running in
S/W
mode
xxxx – 1587
.
19
The data rate in this mode is 9600 baud.
The theoretical number of units that can be connected is sixteen but it
is depending on the type and the number of the units respectively, the
cable type and length, etc.
Connections according to dwg 512-47.
19
For more information about each type of unit, see chapter "Other units",
page 57.