Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
154
In case of charger out of work the following fault message will
be shown:
FAULT: Charger control unit xx
In order to not damage the batteries, the voltage output will be
switched off at approx. 20.8 V. This only happens in case of
no main power source (230 V AC), i.e. when the backup
batteries are used as power source.
If the battery voltage is below 10 V (5 V per battery), the
battery charging will be turned off. (The batteries are
damaged and have to be changed.)
In case of no mains and after a time delay of 1-300 minutes
(programmable in Win512 version 2.7.x but max. 30 min.
according to the EN54-2 standard), the following fault
message will be shown:
FAULT: Mains, control unit xx
26.2
Current consumption calculations
For each control unit, in order to get a current consumption overview
so that the rectifier will not be overloaded and to check / calculate the
required battery capacity, the total EBL512 G3 current consumption
(excl. battery charging current) have to be calculated.
NOTE!
There
is no battery charging during fire alarm.
Use the values in chapter "Current consumption", page 148, to
calculate the following current consumptions:
I
CN
= current consumption for the control unit
134
in normal
state.
I
RN
= current consumption for all other equipment
135
in
normal state.
I
CA
= current consumption for the control unit
134
in alarm
state.
I
RA
= current consumption for all other equipment
136
in
alarm state.
The total EBL512 G3 current consumption in
Normal
(
quiescent
)
state
:
I
TN
=
I
CN
+
I
RN
The total EBL512 G3 current consumption in
Alarm
(
activated
)
state
:
I
TA
=
I
CA
+
I
RA
Comments regarding (
I
TN
):
134
Including the COM loop units but excl. the battery charging current.
135
External equipment connected to the control unit (e.g. ext. FBPs, door
release magnets, relays, routing equipment, etc.).
136
External equipment connected to the control unit (e.g. ext. FBPs,
sounders, relays, routing equipment, etc.).