Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
120
Output for routing equipment (Fire brigade tx) not activated.
18.2
Battery faults
For other conventions, see chapter "Security functions", page 153.
18.2.1
FAULT: Battery
The following battery check is performed:
The battery charging is turned off every 30
th
second.
Battery voltage is checked.
Battery voltage < 18.9 V generates a fault.
Fault message:
FAULT: Battery
18.2.2
FAULT: Low battery capacity
The following battery check is performed:
The battery charging is turned off 60 minutes every 24
th
hour.
Battery voltage is checked during this 60 minutes period.
Battery voltage < 24.4 V generates a fault.
Fault message:
FAULT: Low battery capacity
If a fault is generated it will be
Serviced
after the 60 minutes
period.
18.3
Routing equipment isolate (disable)
If any Fire alarm output for routing equipment (Fire brigade tx or
Fault tx) is disabled and you are closing the c.i.e. door, the built-in
buzzer will beep for two seconds. In the display will be shown:
"Routing equipment left disabled"
. This message has
lower priority than fire alarms but higher than other disablements and
faults.
18.4
Acknowledged alarm
When a fire alarm is activated in the c.i.e. it can be acknowledged by
pressing the soft key "Acknowledge alarm" on the c.i.e. front.
An acknowledged alarm has the same functionality as a normal fire
alarm except for the indication in the c.i.e. display.
In the fire alarm list (presented in the display) will
"ALARM"
be
changed to
"
ACKNOWLEDGED
"
.
An example: