Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
93
FAULT: Loop unit zone: xxx addres:xx
Technical number xxxxxx
16.8
Minimum / Maximum sensor values
To find out how the environment is, where an analog detector 33xx /
430x (in NORMAL mode) is mounted, the
minimum and maximum
sensor values
can be studied. The sensor values are continuously
picked up and evaluated by the control unit (c.i.e.) for each detector
individually. Every value is checked if it is a new minimum or
maximum value for that detector. At midnight every day a memory
will be updated and the new minimum and maximum sensor values
can be read in menu H4/U4
85
.
For analog smoke detectors the minimum and maximum sensor values
are shown as XX.X % (obscuration) per meter.
For analog heat detectors the values are shown as XX°C.
85
I.e. the min. / max. sensor values shown, are from the previous day.