Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
50
4313
no. 00
4313
no. 01
no. A
no. B
Segment A
Segment B
Segment C
EBL512 G3
A-dir.
B-dir.
Figure 9. Two 4313 isolators connected to a COM loop gives
three loop segments, i.e. Segment A (A-00), B (00-01) and C
(01-B). If more isolators have to be added, the sequence
numbers have to be updated (via Win512 version 2.7.x), e.g. if
one isolator is put in between isolator no. 00 and no. 01 in the
figure, the new isolator has to be no. 01 and the old no. 01 has
to be no. 02.
Short circuit / cut-off (break) on the COM loop
See chapter "COM loop units", page 37. See also EBL512 G3
Operating Instructions, chapter "Fault messages".
9.1.5
Units for Hazardous (Ex) areas
In hazardous (Ex) areas,
I
ntrinsically
S
afe (IS) and approved products
are required. The IS alarm points are connected to an interface outside
the Ex area.
Normally the analog addressable units (IS smoke and heat detectors)
shall be used, else conventional units (e.g. IS manual call point).
Analog / addressable units are connected to a COM loop via an IS
barrier unit 2842. See also drawing 512 G3 – 31.
9.1.5.1
Galvanic isolators / IS barrier units
MTL5061
Galvanic isolator (2820). The isolator is used to connect
conventional IS detectors and manual call points to an
expansion board 4580 zone line input (programmed in
"Resistor-Ex" mode). The isolator has two zone line inputs and
two outputs (Channel 1 & 2) and it is mounted in a Waterproof
box (IP66/67). Four compression glands for the cable entries
and an end-of-line resistor (10K) with an area >230 mm
2
are
supplied. Box dimensions (L x W x H): 175 x 125 x 150 mm.
BASEEFA classification: EEx ia IIC T
amb
=60°C.
2842
Intrinsically safe (IS) barrier unit.
40
The barrier unit is used to
connect analog addressable IS detectors to a COM loop. The
unit has connectors for COM loop in / out, external power
supply (24 V DC, 50 mA) and one IS COM line for connection
of up to 20 IS detectors 2840 and 2841. It is mounted in a
Waterproof box (IP66/67). Five compression glands for the
40
This unit might still be under construction.