Panasonic Eco Solutions Nordic AB
MEW01472
Rev: -
Planning Instructions Fire alarm system EBL512 G3, United version 2.7.x
101
The detectors in an
AAF zone
can be one to five and not be
programmed as 2-unit-dependent and not be controlled by the Alert
Annunciation function.
Only Analog photo electric smoke detector 4301 and Analog multi
detector 4300 can be used for
AAF
. If the Analog multi detector 4300
is used, it must be programmed as type "Two addresses", so that only
the "smoke part" of the detector can be used for
AAF
.
Max. 100
AAF zones
(00-99) per c.i.e.
The
AAF buzzer
(e.g. Sounder base 3379) has to be programmed
with the trigger condition "AAF zone alarm" (and maybe other trigger
conditions).
16.14
Quiet alarm
Quiet alarm is normally used in conjunction with the I/O Matrix board
4582
94
, an application board for fan control
95
and an I/O unit 3361 for
fan control.
Smoke detectors, programmed for quiet alarm (via Win512 version
2.7.x), can be used e.g. for controlling fans (stop / start depending on
the type of fan).
NOTE!
Normal fire alarm will not be activated.
Indications and actions:
Detector LEDs are turned on (i.e. also a connected ext. LED).
In the c.i.e. display:
Quiet alarm detector ZZZ-AA
and a user definable alarm text, if programmed.
LEDs "Fire" in the c.i.e. are blinking (0.4 / 0.4 sec.).
Buzzer in the c.i.e. sounding (0.8 / 5 sec.).
Programmable outputs for quiet alarm, e.g. 3361 outputs
controlling supply air fans and standard fans i.e. any output
with a control expression containing trigger conditions "Quiet
Alarm Zone" or "Quiet Alarm Zone Address".
Quiet alarms are non-latching, i.e. they will be automatically reset
when the alarm point / zone is no longer above alarm level.
NOTE!
Quiet alarm can also be programmed for a 3361 unit "zone
line input". In such a case only non-latching detectors can be used.
16.15
Fire alarm type A and Fire alarm type B
Normally the c.i.e. relay output "Fire alarm" is used for Fire alarm
routing equipment (Fire brigade tx). This output is activated for fire
alarm from any alarm point or zone line input (General fire alarm).
94
See "I/O Matrix board 4582", page 31.
95
The Fan control panel 4593 can be used for control of up to eight fans.