3.2 Wiring Diagrams
Please connect a breaker or a fuse to the power supply and voltage input part for safety reasons and to
protect the device.
・
Recommended breaker: 3 to 15A
・
Recommended fuse : Time-lag fuse rated current 2A
Grounding the secondary side of VT (Voltage transformer) and CT (Current transformer) is not
necessary with low-voltage circuit.
*When using several CTs, set each CT approximately 1m apart. If the two CTs are set too close each
other, it may not measure accurately due to magnetic field interference.
◆
When measuring a load with rated input voltage
Single-phase two-wire system
*One CT is needed to measure single-phase two-wire system.
*2 CTs are needed to measure 2-circuit and 3 CTs are needed to measure 3-circuit.
*To measure 2-circuit, wire 3 and 4. To measure 3-circuit, wire 3 and 4 and 5.
Single-phase three-wire/Three-phase three-wire
*2 CTs are needed to measure single-phase three-wire system, three-phase three-wire system.