38
Active power alarm threshold (OUT1 OUT2)
* It is only when [AL-P] is selected for unit for pulse output.
Set a value of instantaneous active power to use for alarm output.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.0 to 2999999.9 (initial: 2999999.9)
Increase
Decrease
Active power alarm OFF threshold (OUT1 OUT2)
* It is only when [AL-P] is selected for unit for pulse output.
Set a value of instantaneous active power to use for clear the alarm output.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.0 to 2999999.9 (initial: 2999999.9)
Increase
Decrease
Reactive power alarm threshold (OUT1 OUT2)
* It is only when [AL-Q] is selected for unit for pulse output.
Set a value of instantaneous reactive power to use for alarm output.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.0 to 2999999.9 (initial: 2999999.9)
Increase
decrease
Reactive power alarm OFF threshold (OUT1 OUT2)
* It is only when [AL-Q] is selected for unit for pulse output.
Set a value of instantaneous reactive power to clear the alarm output.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.0 to 2999999.9 (initial: 2999999.9)
Increase
decrease