82
6.2.11 Current
・
The present current value is displayed. (N-phase current is displayed for 3P4W.)
・
It measures from 0.1% of CT secondary current.
・
When input current exceeds 200% or the display range, it displays “- - - - -“.
Check and confirm the measurement environment.
・
Current measuring points Eco-POWER METER measures the current as below.
Display
1P2W
1P3W
3P3W
3P4W
1
1
st
circuit R-current
R-current
R-current
2
2
nd
circuit R-current
N-current
S-current
3
3
rd
circuit R-current
T-current
T-current
A
Average
Average of R and T
Average
N
-
-
N-current *only 3P4W
6.2.12 Voltage
・
The present voltage is displayed.
・
Press <SHIFT/
▽
> to change phase voltage and line voltage.
(Line voltage is not displayed for 1P2W system. Phase voltage is not displayed for 3P3W system.
Phase voltage Line voltage
・
When input voltage is under 3V (when VT ratio is 1.), it displays “0.0” and doesn’t measure.
・
When input voltage exceeds 600V or the display range, it displays “- - - - -“.
Check and confirm the measurement environment.
・
Voltage measuring points Eco-POWER METER measures the voltage as below.
Display
1P2W
1P3W
3P3W
3P4W
1
R-voltage (L1-N)
or 1
st
circuit R-voltage
R-voltage (L1-N)
No display
R-voltage (L1-N)
2
None or
2
nd
circuit R-voltage
None
S-voltage (L2-N)
3
None or
3
rd
circuit R-voltage
T-voltage (L3-N)
T-voltage (L3-N)
A
Average
Average of R and T
Average
1 2
No display
R-voltage (L1-N)
RS-voltage (L1-L2)
RS-voltage (L1-L2)
2 3
T-voltage (L3-N)
ST-voltage (L2-L3)
ST-voltage (L2-L3)
3 1
TR-voltage (L3-L1)
TR-voltage (L3-L1)
TR-voltage (L3-L1)
A
Average
Average of R and T
Average
Average