18
Chapter 4 Settings
You can set parameters for measuring and the other functions using the keys on Eco-POWER METER.
After wiring Eco-POWER METER and CT, power on and set the parameter for power measurement,
Eco-POWER Meter can measure the electric power. In order to use the other functions, set other
parameters according to your use.
◆
Keys’ functions at setting mode
<MODE>
Shift to setting mode
<SET>
Set the items and values
<SHIFT/
▽
>, <ITEM/
△
>
Select items and change values
◆
Parameters for power measurement
Item
Range
Initial value
Phase/Wire system
1P2W, 1P3W, 3P3W 3P4W
1P2W
CT type
1, 5 [A]
5A
Primary side current of CT
1 to 65535 [A]
5A
Rated voltage
100 to 500 [V]
100V
VT ratio
1.00 to 600.00
1.00
Over voltage (ON threshold)
100.0 to 120.0 [%]
105.0%
Over voltage (OFF threshold)
100.0 to 120.0 [%]
105.0%
Under voltage (ON threshold)
5.0 to 100.0 [%]
95.0%
Under voltage (OFF threshold)
5.0 to 100.0 [%]
95.0%
Over current (ON threshold)
0.1 to 120.0 [%]
100.0%
Over current (OFF threshold)
0.1 to 120.0 [%]
100.0%
Under current (ON threshold)
0.0 to 100.0 [%]
0.0%
Under current (OFF threshold)
0.0 to 100.0 [%]
0.0%
Conversion rate (P) total
0.00 to 99.99/1kWh
10.00
Conversion rate (P) time-zone1
Conversion rate (P) time-zone2
Conversion rate (P) time-zone3
Conversion rate (P) time-zone4
Conversion rate (-P) total
Conversion rate (-P) time-zone1
Conversion rate (-P) time-zone2
Conversion rate (-P) time-zone3
Conversion rate (-P) time-zone4
◆
Parameters for demand measurement
Item
Range
Initial value
Power demand type
Peak (Peak demand),
Slide (Sliding block),
Fixed (Fixed block),
30min (30-min demand)
Peak
Power demand interval 1
1 to 60 [min.]
15
Power demand interval 2
1 to 60 [min.]
1
30-min demand calculation
method
Add (addition), Avg (average)
Add
Power input
CT (CT input), PM (Pulse input)
CT
Pulse unit
kWh (electric power),
PLS (pulse constant)
kWh
Pulse rate
(convert to electric power)
0.001 to 100.000 [kWh]
1.000
Pulse constant number
50000[pulse/kWh], 2000[pulse/kWh]
50000
Current interval
1 to 60 [min.]
15
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]