29
Under current / Under current 2
Set a ratio of current for rated current used for threshold to judge under current and to clear the
under current.
At [under curr] window set a ratio of current to judge under current.
Press <ITEM/
△
>, <SHIFT/
▽
> to set the ratio.
[Set range] 0.0 to 100.0% (initial: 0.0)
Increase
decrease
Press <SET>, and [under curr 2] is displayed. At this window, set a ratio of current to clear under
current.
Press <ITEM/
△
>, <SHIFT/
▽
> to set the ratio.
[Set range] 0.0 to 100.0% (initial: 0.0)
Increase
decrease
ex.) Settings; [under curr] 95.0%, [under curr 2] 100.0%
When measured current is under 95.0%, it judges under current and output alarm.
During output the alarm, if the measured current becomes 100.0%, it will clear the alarm.
Conversion rate (P)
Set the conversion rate per integral active power 1 kWh.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[set range] 0.00 to 99.99/1kWh (initial:10.00)
increase
decrease
Conversion rate (-P)
Set the conversion rate per integral export power (-P) 1kWh.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[set range] 0.00 to 99.99/1kWh (initial:10.00)
increase
decrease