Power input type
*It is only when [30min] is selected for power demand type.
Select input type to use for demand measurement, current measurement or pulse input.
‘CT’; Use current measurement via CT for demand measurement.
‘PM’; Use pulse input for demand measurement.
Count value by pulse input2 is used for power input.
Press <ITEM/
△
>, <SHIFT/
▽
> to select.
[Set list] CT(current measurement),
PM(Pulse input) (initial: CT)
Pulse type
*It is only when [PM] is selected for power input type.
Select pulse type to input.
‘kWh’; Set electric power value per 1-pulse directly.
‘PULSE’; Use pulse constant value of pulse output device to use.
Press <ITEM/
△
>, <SHIFT/
▽
> to select.
[Set list] kWh, PULSE (initial: kWh)
Pulse rate (electric power conversion)
* It is only when [kWh] is selected for pulse type.
Set electric power value per 1-pulse.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.001 to 100.000 [kWh]
Increase
Decrease
Pulse constant value
* It is only when [PULSE] is selected for pulse type.
Select pulse constant value input by an outer pulse detector.
Check and select the pulse constant value of using pulse detector.
Press <ITEM/
△
>, <SHIFT/
▽
> to select.
[Set list] 50000(pulse/kWh), 2000(pulse/kWh)
(initial: 50000)