background image

54 

4.4.6  Settings for time program 

Time program 1 to 10 

You can set 10-type time program. 
Set start time and end time for each time-zone and use it with setting conversion rate. 

Refer to 5.2 Time-zone setting function in detail. 

*End time

Start time of PG-2 is set as the end time of PG-1. 

It means that the end time of PG-n is the same as the start time of PG-(n+1). 

Press <SET> and ‘time-zone’ is blinking. Press <ITEM/

>, <SHIFT/

> to select the time-zone. 

After that press <SET>, and ‘program start-time’ is blinking. Set hour and minute. 

Same time period can’t be set to the different programs. 

Press <ITEM/

> to change program number. 

[Display explanation] 

Program number; PG-1 to PG-10 

time-zone; T1, T2, T3, T4, OFF 

Program start time 

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание AKW92112

Страница 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 2: ...red in these specifications Do not dismantle or remodel the product It could lead to abnormal exothermic heat or smoke generation Do not touch the terminal while turning on electricity It could lead to an electric shock Use the external devices to function the emergency stop and interlock circuit Connect the wires or connectors securely The loose connection might cause abnormal exothermic heat or ...

Страница 3: ...r purchasing KW9M Eco POWER METER In this manual we explain the usage of KW9M Eco POWER METER in detail Please use it correctly after understanding the content enough Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 4: ...t 33 4 4 4 Settings for communication 47 4 4 5 Settings for optional functions 49 4 4 6 Settings for time program 54 4 4 7 Settings for calendar timer 55 4 4 8 Password setting 56 4 4 9 Confirmation window 57 Chapter 5 Various Functions 58 5 1 Pulse output function 58 5 1 1 Output depends on integral electric power 58 5 1 2 Stand by alarm 58 5 1 3 Under voltage alarm 58 5 1 4 Over voltage alarm 58...

Страница 5: ...tegral export power 86 6 2 24 Temperature 87 6 2 25 Calendar timer 87 6 3 Working of Logging Mode 88 6 3 1 Max demand value 93 6 3 2 Max Min value of electric power 94 6 3 3 Integral power 95 6 3 4 Max Min value of each measured value 96 6 4 Working of Demand Mode 98 6 4 1 Peak Demand 98 6 4 2 Block Interval Demand Sliding block fixed block 98 6 4 3 30 min Demand 100 Chapter 7 How to update the fi...

Страница 6: ...fire and an electric shock Connect to the power supply in compliance with the rating Refer to the wiring diagram to ensure proper wiring for the power supply input and output Do not perform wiring or installation with a live line It may also lead to circuit burnout or fire by way of the secondary CT side opening Installation Eco POWER METER is designed to be used in a control panel The power suppl...

Страница 7: ...ad Static electricity Discharge static electricity touching the grounded metal etc when you touch the unit Excessive static electricity might be generated especially in a dry place Cleaning Wipe dirt of the main unit with soft cloth etc When thinner is used the unit might deform or be discolored Power supply Connect a breaker to the voltage input part for safety reasons and to protect the device T...

Страница 8: ...is designed chiefly to manage saving energy It is neither intended nor can it be legally used for billing Model number AKW92112 Model name KW9M Eco POWER METER Advanced type 1 1 Measurement outline Phase Wire system Single phase two wire Single phase three wire Three phase three wire Three phase four wire 1P2W 1P3W 3P3W 3P4W common Applicable power system 100V system 200V system 400V system Measur...

Страница 9: ...ax value Min value Power factor 1 000 to 1 000 Present value Max value Min value Frequency Hz 0 00 to 99 99 1 Present value Max value Min value Pulse count value 0 000 to 99999999 Present value Power conversion value 0 000 to 99999999 Present value Temperature degree C 100 0 to 100 0 1 Present value Calendar January 1 2000 00 00 00 December 31 2099 23 59 59 Present value 1 Display data range is th...

Страница 10: ...e stamp Power 12 records for 12 month Current 12 records for 12 month Voltage 12 records for 12 month Power factor 12 records for 12 month Frequency 12 records for 12 month Unbalanced current 12 records for 12 month Unbalanced voltage 12 records for 12 month Max demand value active power reactive power apparent power export active power export reactive power current with time stamp 12 records for ...

Страница 11: ...udge as under current Over current Set the ratio for the rated current and it is used for threshold Current over the set ratio is kept 100ms or more it will judge as over current Demand by IEC61557 12 Based on IEC61557 12 Performance measuring and monitoring devices PMD Sliding block interval demand It calculates by measured power via CT with setting interval Set power interval by 1 to 60 min ever...

Страница 12: ...suring value Setting mode Indicate the setting value 8 Key Use to operate the unit 9 Terminal A 10 Terminal B 11 USB port USB communication port 12 Mounting clip Use to panel mounting screws M4 10mm 13 Log indication Logging mode Indicate log type 14 Pulse output Indicator Measuring mode Logging mode Demand mode Lighting when pulse is output 15 Pulse input Indicator Measuring mode Logging mode Dem...

Страница 13: ...de Select a setting value Logging mode Select logging item to display Demand mode Select demand item to display SET SHIFT Measuring mode Select measuring item to display Logging mode Select logging item to display Demand mode Select demand item to display MODE SHIFT Measuring mode Shift to logging mode Logging mode Shift to demand mode Demand mode Shift to measuring mode SET ITEM Measuring mode Se...

Страница 14: ...7 2 3 Indication on KW9M Eco POWER METER The alphabet is shown as below Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 15: ...inal block A Terminal number 1 2 3 4 5 6 7 8 9 10 Functions L N V1 V2 V3 Vn NC SG A B Power supply Measured voltage input vacant RS485 Do not use NC vacant terminals in any purpose Terminal block C Terminal number 1 2 3 4 5 6 7 8 Functions OUT1 COM1 OUT2 COM2 IN1 IN1 IN2 IN2 Output 1 Output 2 Input 1 Input 2 It is insulated between OUT1 and OUT2 Minus terminals of input terminal are connected inte...

Страница 16: ... is recommended Stripping length 7 to 8mm Power supply Measured voltage RS485 communication Terminal block A Screw size M2 5 Tightening torque 0 4 to 0 5N m Sectional area single stranded wire 0 5 to 4mm2 AWG20 to12 for 2pcs single stranded wire 2pcs 0 5 to 2mm2 AWG20 to 14 Use shielded wire for RS485 communication Output Input Terminal block C Screw size M2 Tightening torque 0 2 to 0 25N m Sectio...

Страница 17: ...f the two CTs are set too close each other it may not measure accurately due to magnetic field interference When measuring a load with rated input voltage Single phase two wire system One CT is needed to measure single phase two wire system 2 CTs are needed to measure 2 circuit and 3 CTs are needed to measure 3 circuit To measure 2 circuit wire 3 and 4 To measure 3 circuit wire 3 and 4 and 5 Singl...

Страница 18: ...ounded When measuring a load with exceed input voltage Voltage transformer VT is needed when you measure a load with over input voltage Use a VT those secondary voltage rating is 110V Grounding the secondary side of VT and CT is not necessary with low voltage circuit Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 19: ... a load electric wire Incorrect order might cause an electric shock or break CT The CT has polarity Wire correctly according to the K and L marks Wrong direction can t measure correctly If there is some distortion by harmonic or waveform it may not measure correctly Please check with the actual system before adopts it Separate the wiring strong electric part of the measured voltage input terminal ...

Страница 20: ...side current of using CT is 1A 2 Set the primary current of measured CT at primary side current of CT setting mode CT 1 ex If the measured CT is 400A 1A or 400A 5A set to 400 3 Connect CT according to the CT direction power side K to load side L Load Secondary current Breaker Ammeter etc Power supply CT with 2nd current 1A 5A k l K L Without Ammeter Connect CT wiring and terminal block surely It w...

Страница 21: ... transistor is ON Short circuit impedance should be less than 1kΩ Open circuit impedance should be more than 100kΩ When the impedance is 0Ω drain current is approx 10mA Input wiring Please wire as short as possible by using a shielded wire or a metallic electric wire tube individually 3 5 For Output Connection PhotoMOS relay output It adopts PhotoMOS relay output there is no polarity Output Rated ...

Страница 22: ...tor between A and B of Eco POWER METER that is connected the end of RS485 transmission line The RS485 transmission line shielded cable should be grounded at the end KW9M Eco POWER METER Fig 1 Be sure to connect with daisy chain the RS485 transmission line between each unit Do not use a splitter Fig 2 To avoid noise separate the transmission line from high voltage line power supply voltage line Fig...

Страница 23: ...e Max 25 1Ω km PVC Max 0 6 mm Approx 6 6 mm VCTF 0 75 mm2 2C JIS Cable Section Notes 1 Use shielded type twist cables 2 Use only one type of the transmission cables 2 Do not mix different types of the cables 3 Use twist pair cables under a bad noise environment Twisted pair with shield VCTF 3 7 Backup Battery for Clock It is possible to backup the clock with backup battery for 1 month In order to ...

Страница 24: ...e insulation with RS485 communication system side 2 Provide the voltage input part with an EN60947 1 or EN60947 3 compliant circuit breaker 3 Use a wire with basic insulation or more for a wire cramped or connected CT 4 Vn terminal should be connected to N phase which is grounded Environmental conditions Overvoltage category Ⅱ Pollution degree 2 Indoor use An ambient temperature of 25 to 55 An amb...

Страница 25: ...reshold 0 1 to 120 0 100 0 Over current OFF threshold 0 1 to 120 0 100 0 Under current ON threshold 0 0 to 100 0 0 0 Under current OFF threshold 0 0 to 100 0 0 0 Conversion rate P total 0 00 to 99 99 1kWh 10 00 Conversion rate P time zone1 Conversion rate P time zone2 Conversion rate P time zone3 Conversion rate P time zone4 Conversion rate P total Conversion rate P time zone1 Conversion rate P ti...

Страница 26: ...P Stand by alarm threshold OUT1 OUT2 0 1 to 100 0 100 0 Stand by alarm start time OUT1 OUT2 0 to 9999 sec 0 Stand by alarm phase OUT1 OUT2 Phase1 Phase2 Phase3 All All Power alarm active reactive apparent threshold ON OFF OUT1 OUT2 0 0 to 2999999 9 kW kvar kVA 2999999 9 PF alarm threshold ON OFF OUT1 OUT2 0 000 to 1 000 0 000 Over frequency alarm threshold ON OFF OUT1 OUT2 0 00 to 100 00 Hz 100 00...

Страница 27: ...ission speed 38400 19200 9600 4800 2400 1200 bps 19200 Transmission format 8b o 8bit odd 8b n 8bit none 8bit E 8bit even 8b o Stop bit 1 2 1 Response time 1 to 99 ms 5 Parameters for optional functions Item Range Initial value Auto off 0 to 99 min 1 Luminance 1 2 3 4 5 1 dark to 5 light 3 Alarm blinking ON OFF OFF Update cycle 100 to 1000 ms 100 Auto display 0 to 99 min 10 Display cycle 1 to 99 se...

Страница 28: ...4 OFF T2 start time 00 00 to 23 59 16 00 Program 8 time zone T1 T2 T3 T4 OFF T3 start time 00 00 to 23 59 22 00 Program 9 time zone T1 T2 T3 T4 OFF OFF start time 00 00 to 23 59 Program 10 time zone T1 T2 T3 T4 OFF OFF start time 00 00 to 23 59 Initial setting for time program KW9M 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 T1 T2 T3 T4 1 term PG 1 2 term PG 2 3 term PG 3 4 te...

Страница 29: ...er Primary side current of CT Power demand interval 2 1 Pulse input 2 Transmission speed Rated voltage Calculation method for 30 min demand 2 Pre scale 1 4 Transmission format VT ratio Power input type 2 Pre scale 2 Stop bit Over voltage Pulse type 2 Pulse output 1 Response time Under voltage Pulse rate electric power conversion 2 Pulse output 2 Over current Pulse constant value 2 Under current Cu...

Страница 30: ...tting confirmation YES Measuring value display Press SET during each item is displayed to change the setting value Press MODE to display the confirmation window Select YES and press SET to decide the setting value However no value is changed the confirmation window is skipped and it displays the measuring value display 1 It skips when Peak or 30min is set at power demand type 2 It skips when excep...

Страница 31: ...d it shifts to password entry window Enter password from left to right using ITEM SHIFT Increase Shift entered digit to the right Press SET after enter the password If the password is correct it shift to setting mode of power measurement If the password is wrong FAIL is displayed and it returns to the password entry window If you make wrong password 5 times you can t set 1 hour after Phone 800 894...

Страница 32: ...ssword Measuring value display Press MODE and it shifts to password entry window Press MODE and ITEM for 30 seconds in the password entry window and it shift to the password initialize window Not initialize NO Initialize YES Return to the measuring value display 30 seconds Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 33: ...en the system is not matched with the measure system it doesn t measure correctly CT type Select using CT type secondary side current Press ITEM SHIFT to select CT type Set list 5 5A 1 1A initial 5 To use CT with secondary side current 5A 5 To use CT with secondary side current 1A 1 Primary side current of CT Set the primary side current of using CT Enter the primary side current of CT that is set...

Страница 34: ...f voltage for rated voltage used for threshold to judge over voltage and to clear the over voltage At over volt window set a ratio of voltage to judge over voltage Press ITEM SHIFT to set the ratio Set range 100 0 to 120 0 initial 105 0 Increase decrease Press SET and over volt 2 is displayed At this window set a ratio of voltage to clear overt voltage Press ITEM SHIFT to set the ratio Set range 1...

Страница 35: ...e measured voltage becomes over 100 0 it will clear the alarm Over current Over current 2 Set a ratio of current for rated current used for threshold to judge over current and to clear the over current At over curr window set a ratio of current to judge over current Press ITEM SHIFT to set the ratio Set range 0 1 to 120 0 initial 100 0 Increase decrease Press SET and over curr 2 is displayed At th...

Страница 36: ...0 0 to 100 0 initial 0 0 Increase decrease ex Settings under curr 95 0 under curr 2 100 0 When measured current is under 95 0 it judges under current and output alarm During output the alarm if the measured current becomes 100 0 it will clear the alarm Conversion rate P Set the conversion rate per integral active power 1 kWh Press ITEM SHIFT to set set range 0 00 to 99 99 1kWh initial 10 00 increa...

Страница 37: ...and measurement Press ITEM SHIFT to set Set range 1 to 60 min initial 15 Increase Decrease Power demand interval 2 It is only when Slide is selected for power demand type Set slide time to use for sliding block for power demand measurement Press ITEM SHIFT to set Set range 1 to 60 min initial 1 Increase decrease Calculation method for 30 min demand It is only when 30min is selected for power deman...

Страница 38: ...c power value per 1 pulse directly PULSE Use pulse constant value of pulse output device to use Press ITEM SHIFT to select Set list kWh PULSE initial kWh Pulse rate electric power conversion It is only when kWh is selected for pulse type Set electric power value per 1 pulse Press ITEM SHIFT to set Set range 0 001 to 100 000 kWh Increase Decrease Pulse constant value It is only when PULSE is select...

Страница 39: ...and interval Set interval to use for current demand calculation Press ITEM SHIFT to set Set range 1 to 60 min initial 15 Increase Decrease Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 40: ...t IN1 Set time to correct the clock by using pulse input IN1 If KW9M clock is different 1 hour or more from the setting time when pulse is input to IN1 it doesn t correct the clock Press ITEM SHIFT to set Set range 00 00 to 23 59 initial 00 00 Increase decrease Pre scale N1 IN2 It skips when Clock is selected for Pulse input IN1 Set pre scale value used to convert count value of pulse input Press ...

Страница 41: ...Unit for pulse output OUT1 OUT2 Set unit used for pulse output Press ITEM SHIFT to select unit for pulse output To the next page Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 42: ...nt output PL L level output initial 0 001 When one of AL uV under voltage alarm AL oV over voltage alarm AL uC under current alarm AL C current alarm is set alarm is output according to the settings of under voltage over voltage under current over current When AL MS power interruption alarm is set alarm is output when it detects voltage under 5 of rated voltage When PL L level output is set when t...

Страница 43: ...CD All Phase1 Phase2 Phase3 initial All AL PF AL oF AL uF All Phase1 Phase2 Phase3 initial All For 3P3W it can t be selected Setting window is skipped AL C All Phase1 Phase2 Phase3 initial All For 3P4W All Phase1 Phase2 Phase3 Phase n initial All Except Phase n AL uV AL oV AL MS AL VH AL VT All Phase1 Phase2 Phase3 initial All For 3P3W All Line1 2 Line2 3 Line3 1 initial All Selecting All it outpu...

Страница 44: ...ulse output Set a ratio of current for rated current used for threshold to judge stand by power Press ITEM SHIFT to set Set range 0 1 to 100 0 initial 100 0 Increase decrease Stand by power alarm pass time OUT1 OUT2 It is only when AL S is selected for unit for pulse output Set pass time used for threshold to judge stand by power After passing the setting time it will judge as a stand by power Pre...

Страница 45: ... Set range 0 0 to 2999999 9 initial 2999999 9 Increase Decrease Reactive power alarm threshold OUT1 OUT2 It is only when AL Q is selected for unit for pulse output Set a value of instantaneous reactive power to use for alarm output Press ITEM SHIFT to set Set range 0 0 to 2999999 9 initial 2999999 9 Increase decrease Reactive power alarm OFF threshold OUT1 OUT2 It is only when AL Q is selected for...

Страница 46: ...2999999 9 initial 2999999 9 Increase decrease PF alarm threshold OUT1 OUT2 It is only when AL PF is selected for unit for pulse output Set a value of power factor to use for alarm output It judge by using absolute value of measured power factor When measured PF is 0 000 it doesn t output Press ITEM SHIFT to set Set range 0 000 to 1 000 initial 0 000 Increase decrease PF alarm OFF threshold OUT1 OU...

Страница 47: ... set Set range 0 00 to 100 00 Hz initial 100 00 Increase decrease Under frequency alarm threshold OUT1 OUT2 It is only when AL UF is selected for unit for pulse output Set a value of frequency to use for alarm output Press ITEM SHIFT to set Set range 0 00 to 100 00 Hz initial0 00 Increase decrease Under frequency alarm OFF threshold OUT1 OUT2 It is only when AL UF is selected for unit for pulse ou...

Страница 48: ...o set Set range 0 00 to 400 00 initial 400 00 Increase decrease Current harmonics alarm threshold OUT1 OUT2 It is only when AL CH is selected for unit for pulse output Set a value of current harmonics to use for alarm output When one of 2 to 31 order harmonics exceeds the setting threshold it output alarm Press ITEM SHIFT to set Set range 0 00 to 400 00 initial 400 00 Increase decrease Current har...

Страница 49: ...o set Set range 0 00 to 400 00 initial 400 00 Increase decrease Current THD alarm threshold OUT1 OUT2 It is only when AL CT is selected for unit for pulse output Set a value of current THD to use for alarm output Press ITEM SHIFT to set Set range 0 00 to 400 00 initial 400 00 Increase decrease Current THD alarm OFF threshold OUT1 OUT2 It is only when AL CT is selected for unit for pulse output Set...

Страница 50: ...t Set range 0 00 to 999 99 initial 999 99 Increase decrease Current unbalancing alarm threshold OUT1 OUT2 It is only when AL CU is selected for unit for pulse output Set a value of unbalancing to use for alarm output Press ITEM SHIFT to set Set range 0 00 to 999 99 initial 999 99 Increase decrease Current unbalancing alarm OFF threshold OUT1 OUT2 It is only when AL CU is selected for unit for puls...

Страница 51: ...the selected power type Press ITEM SHIFT to set the threshold Set range 0 000 to 99999 999 kWh kvar kVA initial 0 0 P active power P active power import Q reactive power Q reactive power import S apparent power Increase decrease Power demand alarm OFF threshold OUT1 OUT2 It is only when Slide or Fixed is selected for power demand type and when AL PD is selected for unit for pulse output Set a valu...

Страница 52: ... start monitoring power demand Press ITEM SHIFT to set Set range 1 to 30 min initial 10 Increase decrease Current demand alarm threshold OUT1 OUT2 It is only when AL CD is selected for unit for pulse output Set ratio of current demand to use for alarm output Press ITEM SHIFT to set Set range 0 0 to 120 0 initial 0 0 Increase decrease Current demand alarm OFF threshold OUT1 OUT2 It is only when AL ...

Страница 53: ...t1 or Cnt2 is selected for unit for pulse output Set count value to output pulse Press ITEM SHIFT to set Set range 0 0 000 to 999999 999 999 initial 0 Increase decrease Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 54: ...r for each unit when two or more units are connected to communicate via serial communication RS485 Press ITEM SHIFT to set The setting range differs according to the protocol Set range MEWTOCOL 1 to 99 MODBUS RTU 1 to 247 DL T645 2007 0 to 9999 initial 1 increase decrease Transmission speed Baud rate Select the serial communication RS485 transmission speed Define the transmission speed according t...

Страница 55: ...to select Set list 1 2 initial 1 Response time Select 50 or more when 645 is set for the protocol Set serial communication RS485 response time of main unit When command is received it sends response after setting response time passes Press ITEM SHIFT to set Set range 1 to 99 ms initial 5 increase decrease If Data Logger Unit DLU or Data Logger Light DLL is used as a master set the response time to...

Страница 56: ...urn off after setting time 1 to 99 After turns off the LCD any key operation makes it turns on Luminance Adjust the display luminance Press ITEM SHIFT to select Set item 1 2 3 4 5 initial 3 Dark to light from 1 to 5 Alarm blinking Select if the display is blinking during alarm output or not Press ITEM SHIFT to select Set list ON OFF initial OFF Press any key during blinking the display to stop bli...

Страница 57: ...nge 0 to 99 min initial 10 increase decrease Not change automatically 0 Chang automatically after the setting time 1 to 99 Any key operation during auto display makes the display shift to instantaneous active power Display cycle It skips this item when 0 is set for auto display Set each display cycle during auto display Press ITEM SHIFT to set Set range 1 to 99 sec initial 5 increase decrease Shif...

Страница 58: ... Press ITEM SHIFT to select Set list YES NO initial NO Reset all YES Not reset NO Reset integral value 1 It skips this item when YES is selected for reset all integral value Reset the integral power of 1CH 1 phase active reactive apparent and integral export power of 1CH 1 phase active reactive Press ITEM SHIFT to select Set list YES NO initial NO Reset YES Not reset NO Phone 800 894 0412 Fax 888 ...

Страница 59: ... this item when YES is selected for reset all integral value Reset the integral power of 3CH 3 phase active reactive apparent and integral export power of 3CH 3 phase active reactive Press ITEM SHIFT to select Set list YES NO initial NO Reset YES Not reset NO Reset count value 1 It skips this item when YES is selected for reset all integral value Reset the count value 1 Press ITEM SHIFT to select ...

Страница 60: ... reset the electric power converted by pulse Reset log data It skips this item when YES is selected for reset all integral value Reset all log data monthly max min value of measured value max demand power quality event Press ITEM SHIFT to select Set list YES NO initial NO Reset YES Not reset NO Version You can check the software version It displays the software version Phone 800 894 0412 Fax 888 7...

Страница 61: ... means that the end time of PG n is the same as the start time of PG n 1 Press SET and time zone is blinking Press ITEM SHIFT to select the time zone After that press SET and program start time is blinking Set hour and minute Same time period can t be set to the different programs Press ITEM to change program number Display explanation Program number PG 1 to PG 10 time zone T1 T2 T3 T4 OFF Program...

Страница 62: ...blinking in turn With blinking the setting item and press ITEM and SHIFT Caution The timing when the calendar timer is settled to the unit is the timing when you select YES with the confirmation window and press SET It doesn t set the calendar timer to the unit when you press SET with calendar timer setting window Give your attention when you set time by second Phone 800 894 0412 Fax 888 723 4773 ...

Страница 63: ...hange Press SET and 0 on the left is blinking Set password using ITEM SHIFT Increase Shift entered digit to the right Set from left to right Make the digit to set blink Set range 0000 to 9999 initial 0000 Set 4 digit password and press SET After that the confirm window is displayed Set range YES NO initial NO Confirm YES Not confirm NO Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email i...

Страница 64: ...MODE at any setting window and it shifts to confirmation window Set list YES NO initial NO Cancel Confirm Confirm the change YES Cancel the change NO Measuring value display Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 65: ...ing flow chart kW Normal working output turns ON Electric power T threshold C Stand by mode 0 Time min 5 1 3 Under voltage alarm When it falls below the setting voltage pulse output turns on in order to notice When it exceeds the output turns off 5 1 4 Over voltage alarm When it exceeds the setting voltage pulse output turns on in order to notice When it falls below the output turns off 5 1 5 Powe...

Страница 66: ...ol is maintained However output is OFF if count value or preset value is changed Change the Preset Value It is possible to change the preset value even during counting However note the following points When the pre scale value is 1 000 PSCL 1 000 1 If the preset value is changed to the value less than the count value counting will continue until it reaches full scale returns to 0 and then reaches ...

Страница 67: ...th Eco POWER METER Therefore it is different from the demand meter controlled by an electric power company 5 4 1 Peak demand The maximum values of instantaneous power active reactive apparent active export reactive export in one month are recorded as peak demand for 12 month 5 4 2 Block interval demand It calculates demand by setting interval and displays You can select sliding block or fixed bloc...

Страница 68: ... alarm When present demand or estimated demand exceeds the setting threshold for power demand alarm it output alarm present demand or estimated demand threshold for power demand alarm It keeps alarm output for 1 minute after that present demand or estimated demand threshold for power demand alarm Keep alarm present demand or estimated demand threshold for power demand alarm Clear alarm When you se...

Страница 69: ...mand Demand span 30 min t Mask time 1 to 30min no output set at Power demand alarm start time Alarm output Estimated demand kW Threshold kW Present demand kW Estimated demand kW Threshold kW Present demand kW Alarm output Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 70: ...and EV It shows the estimated demand value at the end of demand span according to the using power from the time when demand span starts to present time Calculation addition Estimated demand kW Present demand Power change amount for t minutes P Remaining time minute Sampling cycle t minute Calculation average Estimated demand kW Present demand Remaining time minute Pass time Power demand threshold ...

Страница 71: ...and value It records the max demand value of each time zone and all time for 12 month 5 4 6 Demand alarm output It output with pulse output terminal open collector It output only when AL PD is set for unit for pulse output It doesn t output alarm if power demand alarm threshold is set to 0 000 kW 5 4 7 Working at power failure and at recovery At power failure It stops the demand measurement It rec...

Страница 72: ... during pressing MODE it shifts measuring mode logging mode and demand mode Press MODE to shift the setting mode initial Power monitoring mode MODE MODE SHIFT Log mode MODE Setting mode MODE SHIFT Demand mode MODE MODE SHIFT Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 73: ...eactive Apparent Total integral export power Active Reactive 1st circuit integral power Active Reactive Apparent 1st circuit integral export power Active Reactive 2nd circuit integral power 1 Active Reactive Apparent 2nd circuit integral export power 1 Active Reactive 3rd circuit integral power 1 Active Reactive Apparent 3rd circuit integral export power 1 Active Reactive To next page Phone 800 89...

Страница 74: ... input 1 Pulse input 2 Conversion value P integral power Total 1st circuit 2nd circuit 3rd circuit 1 1 Conversion value P integral export power Total 1st circuit 2nd circuit 3rd circuit 1 1 Temperature Calendar timer Return to instantaneous power 1 When 2nd circuit and 3rd circuit are not measured 0 are displayed Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 75: ...Apparent Total integral export power Active Reactive Phase 1 integral power Active Reactive Apparent Phase 1 integral export power Active Reactive Phase 2 integral power Active Reactive Apparent Phase 2 integral export power Active Reactive Phase 3 integral power Active Reactive Apparent Phase 3 integral export power Active Reactive To next page Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr c...

Страница 76: ...HD Phase voltage THD Line voltage THD Current n order Harmonics 2nd order 3rd order 31st order Phase voltage n order Harmonics 2nd order 3rd order 31st order Line voltage n order Harmonics 2nd order 3rd order 31st order Pulse input value Pulse input 1 Pulse input 2 To next page Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 77: ...al Phase 1 Phase 2 Phase 3 Change time zone Conversion value P integral export power Total Phase 1 Phase 2 Phase 3 Change time zone Temperature Calendar timer Return to instantaneous power Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 78: ...integral power Active Reactive Apparent Total integral export power Active Reactive Current Line voltage Power factor Frequency Current unbalancing Voltage unbalancing Current THD Voltage THD Current n order Harmonics 2nd order 3rd order 31st order To next page Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 79: ...input value Pulse input 1 Pulse input 2 To next page Conversion value P integral power Change time zone Conversion value P integral export power Change time zone Temperature Calendar timer Return to instantaneous power Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 80: ...pparent Total integral export power Active Reactive Phase 1 integral power Active Reactive Apparent Phase 1 integral export power Active Reactive Phase 2 integral power Active Reactive Apparent Phase 2 integral export power Active Reactive Phase 3 integral power Active Reactive Apparent Phase 3 integral export power Active Reactive To next page Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr co...

Страница 81: ...lancing Current THD Voltage THD Current n order Harmonics 2nd order 3rd order 31st order Phase voltage n order Harmonics 2nd order 3rd order 31st order Line voltage n order Harmonics 2nd order 3rd order 31st order Pulse input value Pulse input 1 Pulse input 2 To next page Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 82: ...al Phase 1 Phase 2 Phase 3 Change time zone Conversion value P integral export power Total Phase 1 Phase 2 Phase 3 Change time zone Temperature Calendar timer Return to instantaneous power Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 83: ...ctive power P1 1 Phase 2 integral active power P2 1 Phase 2 total export active power P2 1 Phase 3 integral active power P3 1 Phase 3 total export active power P3 1 Total integral reactive power Q Total integral export reactive power Q Phase 1 integral reactive power Q1 1 Phase 1 integral export reactive power Q1 1 Phase 2 integral reactive power Q2 1 Phase 2 integral export reactive power Q2 1 Ph...

Страница 84: ...it S phase 3 3rd circuit T phase T phase Total 1 2 3 Total R T Total R S T 3P3W Active Reactive Apparent 6 2 6 Instantaneous power of each phase each circuit The present instantaneous power of each phase or each circuit is displayed It doesn t display for 3P3W system Press SHIFT to change phase 1 1st circuit phase 2 2nd circuit and phase 3 3rd circuit 1P2W 1P3W 3P4W Phase 1 1st circuit Phase 2 2nd...

Страница 85: ... zone4 and all time zone are changed in turn It doesn t light with 3P3W system Total integral power is measured and displayed from 0 000 to 29999999 kWh kvarh kVAh The decimal point is changed automatically After reach the full scale 29999999 the value reverts to 0 000 but continues to measure At this window present total integral power is displayed even if integral powers of each phase each circu...

Страница 86: ...and all time zone are changed in turn It doesn t light with 3P3W system Total integral power is measured and displayed from 0 000 to 29999999 kWh kvarh kVAh the decimal point is changed automatically After reach the full scale 29999999 the value reverts to 0 000 but continues to measure At this window present total export power is displayed even if integral powers of each phase each circuit return...

Страница 87: ... zone without setting for any time program is not displayed All time zone Phase1 1st circuit Integral active power Integral reactive power Integral apparent power time zone1 time zone2 time zone3 time zone4 and all time zone are changed in turn Integral power is measured and displayed from 0 000 to 9999999 9 kWh kvarh kVAh The decimal points is changed automatically After reach the full scale 9999...

Страница 88: ...it Integral active power export Integral reactive power export time zone1 time zone2 time zone3 time zone4 and all time zone are changed in turn Integral power is measured and displayed from 0 000 to 9999999 9 kWh kvarh The decimal points is changed automatically After reach the full scale 9999999 9 the value reverts to 0 000 but continues to measure How to reset integral power active reactive app...

Страница 89: ...e voltage is not displayed for 3P3W system Phase voltage Line voltage When input voltage is under 3V when VT ratio is 1 it displays 0 0 and doesn t measure When input voltage exceeds 600V or the display range it displays Check and confirm the measurement environment Voltage measuring points Eco POWER METER measures the voltage as below Display 1P2W 1P3W 3P3W 3P4W 1 R voltage L1 N or 1st circuit R ...

Страница 90: ...be big when it measures unbalanced load 6 2 14 Frequency The present frequency is displayed 1P2W 1P3W 3P4W 3P3W 6 2 15 Current unbalance The present current unbalance is displayed No display for 1P2W 6 2 16 Voltage unbalancing The present voltage unbalancing is displayed No display for 1P2W Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 91: ...resent current n order harmonics is displayed Press SHIFT to change display 2nd order 3rd order 4th order up to 31st order 6 2 20 Voltage n order Harmonics The present voltage n order harmonics is displayed Press SHIFT to change display 2nd order 3rd order 4th order up to 31st order Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 92: ...n value for the present integral active power P is displayed Only total conversion value is displayed for 3P3W system Press SHIFT to change total phase 1 1st circuit phase 2 2nd circuit and phase 3 3rd circuit Press SET to change the display with each time zone After changing press SET to change displayed time zone time zone1 T1 time zone2 T2 time zone3 T3 time zone4 T4 All time zone Time zone wit...

Страница 93: ...T to change the display with each time zone After changing press SET to change displayed time zone time zone1 T1 time zone2 T2 time zone3 T3 time zone4 T4 All time zone Time zone without setting for any time program is not displayed 1P2W 1P3W 3P4W All time zone Total Phase 1 1st circuit Phase 2 2nd circuit Phase 3 3rd circuit time zone1 time zone2 time zone3 time zone4 and all time zone are change...

Страница 94: ...n input current Use it for your reference When the temperature of the front is much different from the temperature of installed panel when it cools inside the panel it is impossible to measure correctly Use the temperature correction function in order to adjust the temperature and use only to check temperature trend 6 2 25 Calendar timer The present date and time is displayed Year ex year 2013 Mon...

Страница 95: ...eactive power demand Apparent power Peak demand this month All time zone time zone time zone time zone time zone Change month Max Apparent power demand Active power export Peak demand this month All time zone time zone time zone time zone time zone Change month Max Active power export demand Reactive power export Peak demand this month All time zone time zone time zone time zone time zone Change m...

Страница 96: ...efore 11 month before Change time zone Integral reactive power All time zone this month 1 month before 2 month before 11 month before Change time zone Integral apparent power All time zone this month 1 month before 2 month before 11 month before Change time zone Integral active power export All time zone this month 1 month before 2 month before 11 month before Change time zone Integral reactive po...

Страница 97: ... 1 month before 2 month before 11 month before Change time zone Phase2 Integral active power All time zone this month 1 month before 2 month before 11 month before Change time zone Phase2 Integral reactive power All time zone this month 1 month before 2 month before 11 month before Change time zone Phase2 Integral apparent power All time zone this month 1 month before 2 month before 11 month befor...

Страница 98: ...power export All time zone this month 1 month before 2 month before 11 month before Change time zone Phase3 Integral reactive power export All time zone this month 1 month before 2 month before 11 month before Change time zone Current This month Max This month Min Change month N phase Current This month Max This month Min Change month Phase voltage This month Max This month Min Change month Line v...

Страница 99: ...Min Change month Voltage unbalancing This month Max This month Min Change month Return to Active power peak demand this month It differs the displayed items according to the phase and wire system Some items are not displayed Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 100: ...ne T1 time zone1 T2 time zone2 T3 time zone3 T4 time zone4 Recorded date and time Ex December 5th 20 18 38 Active power display example Each time zone December All time zone time zone1 time zone2 time zone3 time zone4 are changed in turn Each month December November Change to October September August Press ITEM to change items to display Item Display Indicator unit Active power Peak demand P kW Re...

Страница 101: ... Displayed month Max Min of Phase1 1CH Indicator MAX MIN Max Min of Phase2 2CH Max Min of Phase3 3CH Max Min of total Active power display example Max and Min Max value in December Min value in December Each month Max in December Max in November Change to October September August Press ITEM to change items to display Item Display Indicator unit Active power P kW Reactive power Q kvar Apparent powe...

Страница 102: ...ay Item Display Indicator unit Indicator unit Integral active power P kWh Phase2 Integral active power P2 kWh Integral reactive power Q kvarh Phase2 Integral reactive power Q2 kvarh Integral apparent power S kVAh Phase2 Integral apparent power S2 kVAh Integral active power export P kWh Phase2 Integral active power export P2 kWh Integral reactive power export Q kvarh Phase2 Integral reactive power ...

Страница 103: ...fore If the setting of phase and wire system is changed log data of max and min will be reset Item indicator Displayed month Indicator MAX MIN Average Current display example Max and Min Max in December Min in December N phase Each month December November Change to October September August Press ITEM to change items to display Item Display Indicator unit current I A N phase current I A Phase volta...

Страница 104: ...isplay Item indicator Displayed month Indicator MAX MIN Average Current unbalancing display Item indicator Displayed month Indicator MAX MIN Voltage unbalancing display Item indicator Displayed month Indicator MAX MIN Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 105: ...d Other demand value is not displayed 6 4 2 Block Interval Demand Sliding block fixed block Arrow mark shows to press each key ITEM SHIFT SET SET ITEM Present demand Active power Reactive power Apparent power Present demand export power Active power active Reactive power export Present demand current Return to Present demand Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr ...

Страница 106: ...ween demand time span Until starting next time span at power failure Present export power demand Each demand value is displayed Press SHIFT to change active power export reactive power export Date and time when present demand is measured is displayed in lower 2 lines Active power export Reactive power export present demand present demand is displayed during the following cases Until passing the se...

Страница 107: ...ent current demand Return to active power demand 1 only when PULSE is selected for power input type Active power demand Each demand value is displayed Press SHIFT to change present demand estimated demand demand target value Demand target value is set at Power demand alarm threshold OUT1 OUT2 Present demand Estimated demand Demand target value Present date and time Estimated time 1 OUT1threshold 2...

Страница 108: ... Demand value exceeds the display range Clock is changed between demand time span Until starting next time span at power failure AL PD is not selected for unit for pulse output Integral power converted by pulse Conversion value that pulse from outer pulse detector is converted to electric power is displayed Present value of current demand Present value of current demand is displayed Phone 800 894 ...

Страница 109: ...r It is necessary to install USB driver kw9musb_vxxx inf for connecting KW9M Eco POWER METER via USB communication Once installing USB driver it is not necessary to install from the second time When you change the using port install the driver again Turn on KW9M and connect KW9M and PC via USB cable After that install USB driver according to your OS PC USB cable KW9M Phone 800 894 0412 Fax 888 723...

Страница 110: ...n x xx on the middle line are displayed This is ready to update the firmware of Eco POWER METER 7 2 3 Update the firmware using KW Version Upgrade Tool Connect Eco POWER METER to PC via USB cable 1 Start KW Version Upgrade Tool 2 Select KW9M at Type it changes the window for KW9M 3 Set connected interface with Environmental setting and window appears for setting Port is displayed automatically If ...

Страница 111: ...ad from our website the latest firmware 5 When selected file name is displayed click Update When timed out error is occurred check the below Is Eco POWER METER ready to update Is USB cable connected correctly Are communication port and timeout value conformed Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 112: ...you have used KW Version Upgrade Tool before it displays the last updated firmware If the firmware was moved the error window will be appeared Select firmware again and update it 6 When it starts updating the indicator is appeared and it updates to the selected firmware Do not turn off Eco POWER METER Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 113: ...g When it doesn t update correctly After completing download cell of unit that updating is failure is red On the display of Eco POWER METER PROG is displayed on the upper line and is displayed on the middle line Check and confirm the wiring of Eco POWER METER and so on and update again 9 Click Exit to close KW Version Upgrade Tool You can use Eco POWER METER as it is Phone 800 894 0412 Fax 888 723...

Страница 114: ...istance initial Between the isolated circuits 100 MΩ or more Vibration resistance 10 to 150Hz 7 5 minutes cycle single amplitude 0 075mm 1h on 3 axes 10 to 55Hz 1 minute cycle single amplitude 0 375mm 1h on 3 axes Shock resistance Min 294m s2 5 times on 3 axes Display method LCD with backlight Display updated cycle 100 to 1000ms set with setting mode Power failure memory method Internal memory ove...

Страница 115: ... 600 00 set with setting mode Voltage transformer VT is required when you measure a load with voltage over rated voltage Rated secondary voltage of VT is 110V When it input direct VT ratio is set to 1 00 Current Input current with CT Primary current 65 535A or less Secondary current 1A or 5A set with setting mode Max current 10A 200 of the rating Overload capacity 1000 of the rating for 3s Resolut...

Страница 116: ...er frequency alarm Under frequency alarm Voltage harmonics alarm Current harmonics alarm Voltage THD alarm Current THD alarm Unbalanced voltage alarm Unbalanced current alarm Power demand alarm Current demand alarm counter output level output external control Alarm reset Self reset according to the setting Manual reset Protection element Varistor 1 1 Varistor is mounted internal as a protection el...

Страница 117: ...nce when open Min 100kΩ Input mode IN1 Pulse input or synchronized with input from outer device IN2 Pulse input Max counting speed IN1 30Hz when pulse input IN2 2000Hz 30Hz Min input signal width IN1 16 7m ON OFF ratio 1 1 IN2 0 25ms when 2000Hz is set 16 7ms when 30Hz is set ON OFF ratio 1 1 Pre scale Decimal point Under 3 digit Range 0 001 to 100 000 set with setting mode Output mode when pulse ...

Страница 118: ... Power demand active Estimated demand Demand target value Ratio of estimated demand Current demand Monthly max demand Max demand Saved data Monthly max demand 12 records 12 month Max demand Time span synchronized method Clock synchronized Pulse input to IN1 set with setting mode Synchronized signal input IN1 Input terminal IN1 Input method Non voltage a contact or open collector Pulse width 50ms o...

Страница 119: ... setting mode Stop bit 1bit 2bit select with setting mode 1 MEWTOCOL is the protocol for PLC from Panasonic DL T645 is the China power meter standard Only DL T645 2007 is supported 2 For RS485 converter on the computer side we recommend SI 35 and SI 35USB from LINE EYE Co Ltd When using SI 35 SI 35USB or PLC from our company which can be connected up to 99 units up to 99 can be connected In case u...

Страница 120: ...efore the abnormal 10000000 Memory breakdown or crash Change main unit due to the end of internal memory Includes the possibility that the internal memory life has expired 8 8 Power Failure Memory Eco POWER METER memories integral electric power and working status to internal memory until when power supply is off Power failure guarantee And every time to change each setting each setting value is m...

Страница 121: ...Mounting 9 1 Dimensions 9 1 1 Main unit Unit mm Clearance 1 0 9 2 Panel mounting Unit mm For connected mounting n numbers of mounting units Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 122: ...September 2013 WUME KW9MA 02 2nd edition Add note for theree phase four wire system wiring Add condition for Low voltage directive July 2014 WUME KW9MA 03 3rd edition Add functions Add the reset function with communication Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Отзывы: