20
Item
Range
Initial value
Power demand alarm power
type (ON/OFF) (OUT1,OUT2)
P, Q, S, -P, -Q
P
Power demand alarm
threshold(ON/OFF)(OUT1,OUT2) 0.000 to 99999.999 [kW/kvar/kVA]
0
Power demand alarm
hysteresis (OUT1,OUT2)
0 to 100% [%]
0
Power demand alarm start time
(OUT1,OUT2)
1 to 30 [min.]
10
Current demand alarm
threshold (OUT1,OUT2)
0.0 to 120.0 [%]
0
Preset value (OUT1,OUT2)
0 to 999999
0
◆
Parameters for communication
Item
Range
Initial value
Protocol
MEWTOCOL, MODBUS(RTU),
DL/T645-2007
MEWTOCOL
Device number
MEWTOCOL
1 to 99
1
MODBUS(RTU)
1 to 247
DL/T645-2007
0 to 9999
Transmission speed
38400, 19200, 9600,4800, 2400, 1200 [bps]
19200
Transmission format
8b-o(8bit odd), 8b-n(8bit none),
8bit-E(8bit even)
8b-o
Stop bit
1,2
1
Response time
1 to 99 [ms]
5
◆
Parameters for optional functions
Item
Range
Initial value
Auto-off
0 to 99 [min.]
1
Luminance
1, 2, 3, 4, 5 (1: dark to 5:light)
3
Alarm blinking
ON, OFF
OFF
Update cycle
100 to 1000 [ms]
100
Auto-display
0 to 99 [min.]
10
Display cycle
1 to 99 [sec.]
5
Temperature correction
-100.0 to 100.0
0.0
Reset all integral value
YES, NO
NO
Reset integral value 1
YES, NO
NO
Reset integral value 2
YES, NO
NO
Reset integral value 3
YES, NO
NO
Reset count value 1
YES, NO
NO
Reset count value 2
YES, NO
NO
Reset logging data
YES, NO
NO
Version
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]