4.4.3 Settings for pulse measurement
Pulse input IN1 IN2
Select pulse input max. counting speed or select to use pulse input for clock correction.
Press <ITEM/
△
>, <SHIFT/
▽
> to select.
[Pulse input IN1: Set list]
30(Hz), Clock (clock correction) (initial: 30)
[Pulse input IN2: Set list]
30(Hz), 2000(Hz) (initial: 30)
Clock synchronize
* It skips when [30] is selected for Pulse input IN1.
Set time to correct the clock by using pulse input IN1.
*If KW9M clock is different 1-hour or more from the setting time when pulse is input to IN1, it doesn’t
correct the clock.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 00:00 to 23:59 (initial: 00:00)
Increase
decrease
Pre-scale N1 IN2
* It skips when [Clock] is selected for Pulse input IN1.
Set pre-scale value used to convert count value of pulse input.
Press <ITEM/
△
>, <SHIFT/
▽
> to set .
[Set range] 0.001 to 100.00 (initial: 1.000)
Increase
decrease