26
4.4 How to Set
■
Set before measuring.
Select setting item with <ITEM/
△
> and press <SET>, and the value will be blinking.
Set with <ITEM/
△
> and <SHIFT/
▽
>.
When you select [YES] with the confirmation window and press <SET>, the setting values are
settled.
4.4.1 Settings for power measurement
Phase/Wire system
Select phase/wire system to measure.
Press <ITEM/
△
>, <SHIFT/
▽
> to select phase/wire system.
[Set list] 1P2W, 1P3W, 3P3W, 3P4W (initial: 1P2W)
* When the system is not matched with the measure system, it doesn’t measure correctly.
CT type
Select using CT type (secondary side current).
Press <ITEM/
△
>, <SHIFT/
▽
> to select CT type.
[Set list] 5 (5A), 1 (1A) (initial: 5)
To use CT with secondary side current 5A; [5]
To use CT with secondary side current 1A: [1]
Primary side current of CT
Set the primary side current of using CT.
Enter the primary side current of CT that is set at CT type setting.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 1 to 65535 (initial:5)
Increase
decrease
Primary side current of using CT is 400A: [400]