Option: Remote Heat Duct Kit Installation
This Fireplace is designed to use the optional Pacific Energy Remote Heat Kit (RHKA). This kit allows heat to
be ducted from the casing of the fireplace (using listed B-Vent) to the room or other parts of the home. One
or two Remote Heat Kits may be installed on the fireplace. The Remote Heat Kit includes a blower that will
require an 120V electrical connection.
The Remote Heat Kit requires 6" Listed/Approved B-vent gas venting. This allows reduced clearances in the
wall spaces. Follow the clearances and applicible installation guidelines in the vent manufacturers instruc-
tions, this includes the use of firestops when passing through walls or floor spaces
WARNING: THE CHASE ENCLOSURE MUST HAVE A MINIMUM 30in² (194 cm²) ROOM AIR INLET FOR
EACH REMOTE HEAT KIT INSTALLED ON THE FIREPLACE. The inlets can be combined, but it must
be 60in² or greater. No chase air inlet is required if not installing a remote heat kit, but a single inlet is
recommended for efficiency.
25
100001385_071118-40
FP25