Minimum Framing Dimensions
The top front framing must be installed
as shown, (Figure 7) with no wood
framing directly in front of the chimney
system
WARNING: The fireplace must not be
in contact with any insulation or loose
filling material. If you are insulating the
chase, cover the insulation with drywall
or non-combustible panels. Maintain all
proper clearances.
WARNING: Drywall materials are con-
sidered combustible and theIr thick-
ness must be accounted for in your
framing dimensions.
The open volume inside the chase is
required for heat management. Do Not
build a recess, shelves or cupboards
in the area above this fireplace. Do not
build anything inside this Minimum
chase area.
Do Not insulate the front portion of the
chase above the unit.
24"
610mm
33 3/4"
857mm
96 5/8"
2.45m
23 7/8"
606mm
56 1/2"
1.435m
3 1/8"
79mm
68 3/8"
1.74m
56 1/2"
1.435m
68 3/8"
1.74m
9 3/8"
238mm
NOTE: The framing dimensions shown are the
minimums. Framing dimensions will need
to be adjusted accordingly to accept
drywall/wallboard if used inside enclosure.
Figure 6: FP25 Framing Dimensions.
24”
[610mm]
56 1/2”
[1.435m]
62”
[1.575m]
7’
[2.134m]
Inside Enclosure,
from base of the
unit.
18”
[455mm]
18”
[455mm]
Figure 7: FP 25 framing enclosure.
17
100001385_071118-40
FP25