Ember Protector
This Fireplace requires Non-Combustible Ember Protection extending from face of the unit out in front of the
Door. This can be tile, brick, slate, stone or metal that meets or exceeds UL1618 Type 1 - floor protector.
Minimum 20GA steel
The stove must be installed with ember protection in front of the unit, made from a non-combustible material
with a minimum K value of 23.7 btu/ft h ˚F.. - Equivalent to 20GA steel. This protection must extend as follows:
Safety Strip
The floor between the fireplace and the hearth extension/ember protection must be protected with a 2"
(51mm) deep safety metal strip equal to the width of the unit.
One half of the metal strip must be under the fireplace front and the other half must extend onto the floor and
under the hearth extension/ember protection as shown in Figure 17.
If the unit is raised up then a 2" x 2" angled piece can be used against the non combustible face.
Ember Protection
Fireplace front
Metal safety strip
Hearth extension
non-combustible
finish material
Floor
The space between the fireplace
and the hearth extension must be
sealed with a non-combustible
material such as sand - cement grout
2”
51 mm
Figure 17: Floor safety strip.ai
8” [203mm]
35” [890mm]
Ember
Protection
8” [203mm]
16 1/2” [420mm]
Minimum Width - 35"(889mm) centered with door opening
Minimum Overall Depth - 16 1/2"(420mm)
Figure 18: FP25 Ember protection US.
24
100001385_071118-40
FP25