E-026-3-E
2
(4) If you select "4mA−20mA" on the window shown in Fig. 3-69 and click "OK" button, the window
shown in Fig. 3-71 will be displayed. Select whether 4mA or 20mA should be used for the adjustment.
Here, 4mA adjustment is executed and then 20mA adjustment is executed in order.
Enter the current reading of the ammeter output and click "OK" button.
Fig. 3-71
When the reading is sent, the transmitter automatically adjusts the output to 4mA. Verify that the
connected ammeter indicates 4mA.
If another adjustment is required, enter the reading of the ammeter again on this window and click "OK"
button.
(5) To execute 20mA adjustment, click 20mA side on the window shown in Fig. 3-71 and execute
adjustment so that the connected ammeter indicator reads 20mA in the same manner as 4mA
adjustment.
(6) By clicking "Cancel" button, the adjustment of analog output value will be completed. The message
box "Adjustment is completed" shown in Fig. 3-72 will be displayed. Click "OK" button.
(7) To stop the adjustment during the process, click "Cancel" button and follow the following message.
Fig. 3-72
Click here and select
which adjustment
should be executed.