116
Multi-function Input Selection (n077)
n077 Settings
No.
Name
Unit
Setting
Range
Factory
Setting
n077 Multi-function Input Selection
-
0 to 4
0
Setting
Function
Description
0
Disabled
The multi-function input is disabled.
1
Auxiliary frequency
reference (FREF2)
When frequency reference 2 is select-
ed using the multi-step speed referenc-
es, the input analog signal for the CN2
terminal will be the frequency refer-
ence. The n025 setting will be invalid.
Note: Set the Frequency Reference Gain in
n068 or n071, and the Frequency Ref-
erence Bias in n069 or n072.
2
Frequency refer-
ence gain (FGAIN)
Set the FGAIN to constant n060 or
n074 and the FBIAS to constant n061
or n075 for the master frequency refer-
ence. Then, multiply the resulting fre-
quency reference by the FGAIN.
3
Frequency refer-
ence bias (FBIAS)
Set the FGAIN to constant n060 or
n074 and the FBIAS to constant n061
or n075 for the master frequency refer-
ence.
Then, add the FBIAS to the resulting
frequency reference.
The amount of the FBIAS to be added
is set to n079.
4
Output voltage bias
(VBIAS)
Add the VBIAS to the output voltage af-
ter V/f conversion.