38
Operation Steps
Operator
Display
Function
Indicators
Status
Indicators
1. Turn ON the power supply.
6.00
2. Set constant n004 to 1.
1
3. Set the following constants.
n019: 15.0 (acceleration time)
n020: 5.0 (deceleration time)
15.0
5.0
4. Select forward or reverse run by press-
ing
or
key.
Never select REV when reverse
run is prohibited.
(Forward)
or
(Reverse)
5. Set the reference by pressing
or
key.
60.00
6. Press .
0.00
→
60.00
7. Press
to
stop.
60.00
→
0.00
FREF
RUN
ALARM
PRGM
RUN
ALARM
PRGM
RUN
ALARM
NOTE
F/R
RUN
ALARM
FREF
RUN
ALARM
RUN
FOUT
RUN
ALARM
STOP
FOUT
RUN
ALARM
Status indicators : ON : Flashing (Long flashing) : Flashing : OFF