COPY Function
This function writes the constants stored inside the Digital Operator in
batch to the Inverter. Write-in is possible only for Inverters with the
same product series, power supply specifications, and control mode (V/
f control or vector control).
Therefore, writing from 200 V Class to 400 V Class Inverters (or vice
versa), from V/f control mode to vector control mode Inverters (or vice
versa), or from V7 IP65 to VS mini J7 Inverters is not possible.
The Constant Copy Function Selection (n176), Constant Read Selection
Prohibit (n177), Fault History (n178), Software Version No. (n179), and
hold output frequency are not written. vAE will appear (flashing) if the
capacities of the Inverters differ.
Press
to continue writing (the COPY function).
Press
to stop the COPY function.
The following constants are not written if the Inverter capacities differ.
Constants added with software version upgrades will not be written
between V7 IP65 Inverters without the additional constants and
V7 IP65 Inverters with the additional constants.
For this reason, the settings for the additional constants will not be
changed by the copy operation.
Constant No.
Name
Constant No.
Name
n011 to n017
V/f Settings
n108
Motor Leakage Induc-
tance
n036
Motor Rated Current
n109
Torque Compensa-
tion Voltage Limiter
n080
Carrier Frequency Se-
lection
n110
Motor No-load Current
n105
Torque Compensation
Iron Loss
n140
Energy-saving Coeffi-
cient K2
n106
Motor Rated Slip
n158
Motor Code
n107
Motor Line-to-neutral
Resistance