60
LOCAL Mode
Select the command method using constant n008.
n008=0: Enables using the potentiometer on the Digital Operator.
=1: Enables digital setting on the Digital Operator
(factory setting).
The factory setting for models with the Digital Operator
without potentiometer (JVOP-147) is n008=1.
• Digital Setting Using the Digital Operator
Input the frequency while
is lit (press
after setting the
numeric value).
Frequency reference setting is effective when 1 (factory setting: 0) is set
for constant n009 instead of pressing
.
n009 =0: Enables frequency reference setting using the
key.
=1: Disables frequency reference setting using the
key.
REMOTE Mode
Select the command method in constant n004.
n004 =0: Enables frequency reference setting using the potentiometer
on the Digital Operator.
=1: Enables using frequency reference 1 (n024) (factory setting)
Factory setting of models with the Digital Operator without
potentiometer (JVOP-147) is n004=1.
=2: Enables a voltage reference (0 to 10 V) (refer to the figure
on page 60).
=3: Enables a current reference (4 to 20 mA) (refer to page 120).
=4: Enables a current reference (0 to 20 mA) (refer to page 120).
=5: Enables a pulse train reference (refer to page 122).
=6: Enables communication (refer to page 135).
=7: Enables a voltage reference on Digital Operator circuit
terminal CN2 (0 to 10 V)
=8: Enables a current reference on Digital Operator circuit
terminal CN2 (4 to 20 mA)
=9: Enables communication card (optional).
Example of frequency reference by voltage signal
FREF
ENTER
ENTER
ENTER
ENTER
IM
2 k
Ω
(0 to +10 V)
FS
FR (Master Frequency Reference)
FC (0 V)
n004=2
(factory setting: 1)
(Frequency Setting Power
+12 V 20 mA)
Master
Frequency
Reference