6 Programming Features
49
Constant Setup and Initialization
Constant Selection/Initialization (n001)
If n001=5, a Run Command can be received even
while changing a constant. If sending a Run Com-
mand while changing a constant, such as during a test
run, be sure to observe all safety precautions.
Failure to observe this warning may result in injury.
The following table lists the data that can be set or read when n001 is
set. By setting this constant, the fault history can be cleared and the con-
stants initialized. Unused constants between n001 and n179 are not dis-
played.
* 1. Excluding setting-disabled constants.
* 2. Refer to page 107.
appears on the display for one second and the set data
returns to its initial values in the following cases.
1. If the set values of Multi-function Input Selections 1 to 7
n001
Setting
Constant That Can Be Set
Constant That Can Be Referenced
0
n001
n001 to n179
1
n001 to n049
*1
2
n001 to n079
*1
3
n001 to n119
*1
4
n001 to n179
*1
5
n001 to n179
*1
(Run Command can be received in Program mode.)
6
Fault history cleared
7 to 11
Not used
12
Initialize
13
Initialize (3-wire sequence)
*2
WARNING
NOTE