226
032
0120
Jog Frequency
0.00 to 400.0
Hz
0.01 Hz (less
than 100
Hz)/
0.1 Hz (100
Hz or more)
6.00 Hz
Yes
70
033
0121
Frequency Reference Upper
Limit
0% to 110%
1%
100%
No
72
034
0122
Frequency Reference Lower
Limit
0% to 110%
1%
0%
No
72
035
0123
Setting/Displaying Unit Selec-
tion for Frequency Reference
0 to 3999
-
0
No
176
036
0124
Motor Rated Current
0% to 150% of
Inverter rated
current
0.1 A
(Note 3)
No
130
037
0125
Electronic Thermal Motor
Protection Selection
0 to 4
-
0
No
130,
98
038
0126
Electronic Thermal Motor Pro-
tection Time Constant Setting
1 to 60 min
1 min
8 min
No
130
039
0127
Selecting Cooling Fan
Operation
0, 1
-
0
No
135
040
0128
Motor Rotation Direction
0, 1
-
0
No
39
041
0129
Acceleration Time 3
0.00 to 6000 s Depends on
n018 setting
10.0 s
Yes
73
042
012A
Deceleration Time 3
0.00 to 6000 s Depends on
n018 setting
10.0 s
Yes
73
043
012B
Acceleration Time 4
0.00 to 6000 s Depends on
n018 setting
10.0 s
Yes
73
044
012C
Deceleration Time 4
0.00 to 6000 s Depends on
n018 setting
10.0 s
Yes
73
045
012D
Frequency Reference Bias
Step Amount (Up/Down
Command 2)
0.00 Hz to
99.99 Hz
0.01 Hz
0.00 Hz
Yes
110
046
012E
Frequency Reference Bias
Accel/Decel Rate (Up/Down
Command 2)
0, 1
-
0
Yes
110
047
012F
Frequency Reference Bias
Operation Mode Selection
(Up/Down Command 2)
0, 1
-
0
Yes
110
048
0130
Frequency Reference Bias
Value (Up/Down Command
2)
-99.9% to
100.0%
n011=100%
0.1%
0.0%
No
110
049
0131
Analog Frequency Refer-
ence Fluctuation Limit Level
(Up/Down Command 2)
0.1% to
100.0%
n011=100%
0.1%
1.0%
Yes
110
No. Register
No. for
Trans-
mission
Name
Setting Range Setting Unit
Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page