8 Fault Diagnosis
195
Flashing
Detected as
an alarm
only. Fault
contact out-
put is not ac-
tivated.
CE (MEMOBUS) com-
munications fault
Check the following:
• Communication
devices
or communication sig-
nals.
• PLC is not faulty.
• Transmission cable is
connected properly.
• Any
loose
terminal
screws do not result in
improper contact.
• Wiring is made properly.
Flashing
FBL (PID feedback loss
detection)
PID feedback value dropped
below the detection level
(n137). When PID feedback
loss is detected, the Inverter
operates according to the
n136 setting.
Check the mechanical sys-
tem and correct the cause, or
increase the value of n137.
Flashing
Option card communica-
tions fault.
• Communication fault has
occurred in a mode
where the communica-
tions option card was
used and a Run Com-
mand or frequency refer-
ence was input from the
PLC.
• Communication fault has
occurred in a mode
where a Run Command
and frequency reference
are set from the commu-
nication option card.
Check the following:
• Communications
devices
or communications sig-
nals.
• PLC is not faulty.
• Transmission cable is
connected properly.
• Any
loose
terminal
screws do not result in
improper contact.
• Wiring is made properly.
• Communication
option
card is inserted correctly.
Flashing
OH3 (Inverter overheat
alarm)
The Inverter overheat alarm
(OH3) was input from a multi-
function input terminal (S1
and S7).
• Clear the multi-function
input terminal’s Inverter
overheat alert input.
• Check that the wiring is
made properly.
• Check that a signal is not
input from the PLC.
Alarm Display
Inverter
Status
Description
Causes and
Corrective Actions
Digital
Operator
RUN (Green)
ALARM (Red)
or