232
133
0185
PID Offset Adjustment
−
100% to 100%
1%
0%
Yes
156
134
0186
Upper Limit of Integral Values
0% to 100%
1%
100%
Yes
155
135
0187
Primary Delay Time Constant
for PID Output
0.0 to 10.0 s
0.1 s
0.0 s
Yes
156
136
0188
Selection of PID Feedback
Loss Detection
0 to 2
-
0
No
157
137
0189
PID Feedback Loss Detection
Level
0% to 100%
1%
0%
No
157
138
018A
PID Feedback Loss Detection
Time
0.0 to 25.5 s
0.1 s
1.0 s
No
157
139
018B
Autotuning Selection
0 to 2
-
0
No
61
140
018C
Motor 2 Maximum Output Fre-
quency
50.0 to
400.0 Hz
0.1 Hz
50.0 Hz
No
94
141
018D
PTC Thermistor Input Motor
Overheat Protection Selection
0 to 7
-
0
No
133
142
018E
Motor Temperature Input Filter
Time Constant
0.0 to 10.0 s
0.1 s
0.2 s
Yes
133
143
018F
Sequence Input Redundant
Reading Selection (Stop Posi-
tion Control Selection)
0 to 2
-
0
No
103
144
0190
Stop Position Control Com-
pensation Gain
0.50 to 2.55
0.1
1.00
No
103
145
0191
Bi-directional Function Selec-
tion
0, 1
-
0
No
157
146
0192
Frequency Offset Selection
0 to 29
-
0
No
80
147
0193
Motor 2 Maximum Voltage
Output Frequency
0.2 to
400.0 Hz
0.1 Hz
50.0 Hz
No
94
148
0194
UV fault storage selection
0,1
-
0
No
-
149
0195
Pulse Train Input Scaling
100 to 3300
1 = 10 Hz
2500
(25 kHz)
No
122
150
0196
Pulse Monitor Output
Frequency Selection
0, 1, 6, 12, 24,
36, 40 to 45,
50
-
0
No
87
151
0197
MEMOBUS Timeover
Detection
0 to 4
-
0
No
137
152
0198
MEMOBUS Frequency
Reference and Frequency
Monitor Unit
0 to 3
-
0
No
137
153
0199
MEMOBUS Slave Address
0 to 32
-
0
No
138
No. Register
No. for
Trans-
mission
Name
Setting Range Setting Unit
Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page