39
F3SJ-A
User’s Manual
Chapter
2
Mu
ting Sys
te
m
System Configuration and Functions
E
• T1min: Muting input time limit (minimum value)
This is set to 0.03 sec., the minimum value for the input time difference between muting input 1 and 2.
A muting error occurs when the input time difference between muting input 1 and 2 is less than this
value.
•T1max: Muting input time limit (maximum value)
This is set to 3 sec., the maximum value for the input time difference between muting input 1 and 2.
Minimum value must be less than maximum value.
•T2: Muting time limit
This is set to 60 sec., the muting function continuation time. When this muting state exceeds this time,
muting is released.
•T3: Muting input time with allowable waveform cracks
This is the maximum value for the waveform cracks allowed for muting input 1 and 2 when muting is
in effect. It is set to 0.1 sec.
Muting state can be released if a sensor transitions to lockout as well.
The values shown below can be changed using the PC tool for F3SJ.
•T1min: Muting input time limit (minimum value)
•T1max: Muting input time limit (maximum value)
•T2: Muting time limit
The values shown below can be changed using the setting console.
•T2: Muting time limit
Muting function p.91
# of connections
*1 Value (s)
Single
0.15
2 connected
0.26
3 connected
0.29
4 connected
0.32