What can be done by the setting tool
Muting Zone Setting Example
•Setting from F3SJ’s upper beams (figure 1)
•Setting multiple zones (figure 2)
- Only one zone can be configured as a muting zone by the setting console, which cannot set more than one zone.
- Interlock function is disabled for a muting system.
If you want to use start or restart interlock, use the setting tool to enable the function.
- When muting function is enabled, a muting lamp is turned on to notify people in the surrounding zone that the safety
functions are disabled. Factory setup is external indicator outputs 1 and 2.
While the setting tool allows change of output destination for a muting lamp, muting/override information must be set
to at least one of auxiliary output 1 or external indicator outputs 1 or 2.
If none of the above output is set, F3SJ enters lockout.
- Auxiliary output 1, external indicator outputs 1 and 2 have diagnosis function.
For safety reason, using diagnosis function is recommended.
- Auxiliary Output (Non-Safety Output) p.95
- External Indicator Output (Non-Safety Output) p.99
1. Standard Muting Mode
Operation mode configured for F3SJ factory shipment.
Turning muting inputs 1 and 2 ON with time difference enables muting function.
For details, see Muting in Chapter 2.
Setting can be changed, such as muting time limit.
2. Exit Only Muting Mode (Setting is Available Only for PC Tool For F3SJ)
Turning muting inputs 1 and 2 ON with time difference enables muting function.
Difference from standard mode exists in muting completion condition.
• Start Conditions
If both of the following 2 conditions are present, muting is activated.
1. No interrupting object is found in the F3SJ's detection zone, and safety output is ON.
2. After muting input 1 is turned ON (connected to 9 to 24V), muting input 2 is turned ON (connected to
9 to 24V) within the muting input time limit of T1min to T1max (0.03 to 3s: can be changed).
Lower
Upper
Lower
Upper
Muting zone
Muting zone
Muting zone
Normal detecting beam
Muting beams
Figure 1
Figure 2