91
F3SJ-A
User’s Manual
Ch
apt
e
r
3
Set
ting Adjust
ed
to Appl
ication
What can be done by the setting tool
E
Setting Change
Setting items vary according to the mode.
Muting zone setting: Configure for each CH in case of a series connection.
Other than the above: Configure in a bulk in case of a series connection. (to be written into the primary
sensor only)
Standard muting mode
Exit only muting mode (PC tool for F3SJ only)
Position detection muting mode (PC tool for F3SJ only)
If muting function is enabled, either output mode of external indicator output 1, 2, or auxiliary output 1 must be
configured as shown below.
- Muting information
- Muting/override information
Limitation for Combination with Other Functions
You can use this function in combination with fixed blanking, floating blanking, and warning zone
functions at the same time with the PC tool for F3SJ. Note that there is a limitation for setting with
zones.
The setting console can be combined with fixed blanking function.
For details, see Setting Zone Adjacent Conditions p.92 .
Setting Zone Adjacent Conditions p.92
Function
Initial Setting
Available Setup Item
Setting Console
PC Tool For F3SJ
Muting Zone Setting
All beams
1 to all beams
3
3
T1min: Muting input time limit
(minimum value)
0.03s
0.03s, 0.1s to 3.9s (by 0.1s)
–
3
T1max: Muting input time limit
(maximum value)
3s
0.2s to 4s (by 0.1s)
–
3
T2: Muting time limit
60s
1s to 600s (by 1s) or infinite
3
3
Function
Initial Setting
Available Setup Item
Setting Console
PC Tool For F3SJ
Muting Zone Setting
All beams
1 to all beams
–
3
T1min: Muting input time limit
(minimum value)
0.03s
0.03s, 0.1s to 3.9s (by 0.1s)
–
3
T1max: Muting input time limit
(maximum value)
3s
0.2s to 4s (by 0.1s)
–
3
T2: Muting time limit
60s
1s to 600s (by 1s) or infinite
–
3
T5: Exit only muting delay time
4s
0.1s to 4s (by 0.1s)
–
3
Function
Initial Setting
Available Setup Item
Setting Console
PC Tool For F3SJ
Muting Zone Setting
All beams
1 to all beams
–
3
T1min: Muting input time limit
(maximum value)
3s
0.1s to 4s (by 0.1s)
–
3
T2: Muting time limit
60s
1s to 600s (by 1s) or infinite
–
3