2-4-3 Terminal Block Specifications
Signal
Function
Condition
L1
Main circuits
power supply input
R88D-WT
j
H (30 to 400 W):
Single-phase 200/230 V AC (170 to 253 V AC) 50/60 Hz
R88D-WT
j
HH (750 W to 1.5 kW):
Si l
h
/
V AC (
V AC)
/
H
L2
(
)
Single-phase 220/230 V AC (187 to 253 V AC) 50/60 Hz
R88D-WT
j
H (500 W to 6 kW):
Three-phase 200/230 V AC (170 to 253 V AC) 50/60 Hz
R88D-WT
j
HL (30 to 200 W):
L3
R88D-WT
j
HL (30 to 200 W):
Single-phase 100/115 V AC (85 to 127 V AC) 50/60 Hz
R88D--WT
j
HF (450 W to 15 kW):
Three-phase 380/460 V AC (323 to 528 V AC) 50/60 Hz
+
Main circuit DC
output (Forward)
Do not connect anything. This terminal is for the R88D-WT60H only.
+1
DC Reactor termi-
nal for power sup-
Normally short-circuit b1 and +2.
If harmonic control measures are required connect a DC Reactor between
+2
nal for power sup
ply harmonic con-
trol
If harmonic control measures are required, connect a DC Reactor between
+1 and +2. (The R88D-WT60H does not have this terminal.)
--
Main circuit DC
output (Reverse)
Do not connect anything.
L1C/24 V Control circuits
power supply input
R88D-WT
j
H(H): Single-phase 200/230 V AC (170 to 253 V AC) 50/60 Hz
R88D WT
j
HL: Single phase 100/115 V AC (85 to 127 V AC) 50/60 Hz
L2C/0 V
power supply input R88D-WT
j
HL: Single-phase 100/115 V AC (85 to 127 V AC) 50/60 Hz
R88D-WT
j
HF: 24 V DC (20.4 to 27.6 V DC)
B1
External regenera-
tion resistance
connection termi-
30 to 400 W: This terminal does not normally need to be connected. If
regenerative energy is high, connect an External Regeneration Resistor be-
tween B1 and B2.
B2
connection termi-
nal
tween B1 and B2.
450 W to 5 kW: Short-circuit between B2 and B3. If regenerative energy is
high, remove the short bar between B2 and B3 and connect an External
Regeneration Resistor between B1 and B2
B3
Regeneration Resistor between B1 and B2.
6 to 15 kW: Connect an External Regeneration Resistance Unit between B1
and B2.
U
Servomotor con-
These are the terminals for outputs to the Servomotor. Be sure to wire these
V
nection terminals
p
terminals correctly.
W
Frame ground
This is the ground terminal. Ground to a minimum of 100
Ω
(class-3).