I/O port
Description
Condition
R/
W
Data
type
D00 Normal Op-
erating
Safety programs
operating with no
errors.
All safety master
connections estab-
lished.
This variable is TRUE when all of the following condi-
tions are met. If even one condition is not met, it is
FALSE.
Condition
•
The safety programs are in RUN status (RUN
mode or DEBUG mode (RUN)).
•
No event with a level of minor fault or higher cur-
rently exists for the safety programs.
•
All FSoE connections are established.
•
All the CIP Safety Originator connections are es-
tablished.
•
No error is present in the CIP Safety Target con-
nections.
R
BOOL
D01 Program
Operating
Safety programs
operating
This variable is TRUE when the following condition is
met. If the condition is not met, it is FALSE.
Condition
•
The safety programs are in RUN status (RUN
mode or DEBUG mode (RUN)).
R
BOOL
D02 Program
No Fault
No event with a lev-
el of minor fault or
higher currently ex-
ists for the safety
programs.
This variable is TRUE when the following condition is
met. If the condition is not met, it is FALSE.
Condition
•
No event with a level of minor fault or higher cur-
rently exists for the safety programs.
R
BOOL
D03 Safety
Master
Connection
Status
All safety master
connections estab-
lished.
This variable is TRUE when all of the following condi-
tions are met. If even one condition is not met, it is
FALSE.
Condition
•
All FSoE connections are established.
•
All the CIP Safety Originator connections are es-
tablished.
R
BOOL
D04 FSoE Mas-
ter Connec-
tion Status
All the FSoE safety
master connections
established.
This variable is TRUE when the following condition is
met. If the condition is not met, it is FALSE.
Condition
•
All FSoE connections are established.
R
BOOL
D05 CIP Safety
Originator
Connection
Status
All the CIP Safety
Originator connec-
tions established.
This variable is TRUE when the following condition is
met. If the condition is not met, it is FALSE.
Condition
•
All the CIP Safety Originator connections are es-
tablished.
R
BOOL
D06 CIP Safety
Target Con-
nection
Status
No error in the en-
tire CIP Safety Tar-
get connections
This variable is TRUE when the following condition is
met. If the condition is not met, it is FALSE.
Condition
•
No error is present in the entire CIP Safety Target
connections.
R
BOOL
Appendices
A - 73
NX-series Safety Control Unit User's Manual (Z930)
A-5
Safety CPU Unit
Status
A
A-5-2 NX-SL5500
/NX-SL5700
Содержание NX-SIH400
Страница 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Страница 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Страница 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Страница 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Страница 378: ...7 Checking Operation and Actual Operation 7 72 NX series Safety Control Unit User s Manual Z930 ...
Страница 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Страница 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Страница 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Страница 550: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 38 NX series Safety Control Unit User s Manual Z930 ...
Страница 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 558: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 46 NX series Safety Control Unit User s Manual Z930 ...
Страница 564: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 52 NX series Safety Control Unit User s Manual Z930 ...
Страница 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...