CPU rack settings
Transfer method
Transfer
destina-
tion
Safety ap-
plication da-
ta
Unvalidated
safety appli-
cation data
The safety application data is transferred automatically when you
change to DEBUG mode from the Safety CPU Unit Setup and Pro-
gramming View.
Safety CPU
Unit
Validated
safety appli-
cation data
In DEBUG mode, execute Safety Validation from the Safety CPU
Unit Setup and Programming View. This will cause the safety appli-
cation data to be saved to the non-volatile memory.
Perform the following operation with the Controller set to the NX-
series CPU Unit.
Transfer the NX bus master settings in the Synchronization Win-
dow.
*1.
The entire CPU rack of the NX-series CPU Unit restarts after the NX bus master settings are transferred.
l
Configuration in which the Safety Control Unit is included in the EtherCAT
Slave Terminal
Slave Terminal settings
Transfer method
Transfer
destination
Connection to an NJ/NX-series CPU
Connection to USB
port on EtherCAT
Coupler Unit
EtherCAT
network con-
figuration in-
formation
Perform the following operation with the
Controller set to the NJ/NX-series CPU
Unit.
Transfer the EtherCAT network configura-
tion information from the Synchronization
Window.
Transfer is not al-
lowed.
NJ/NX-ser-
ies CPU
Unit
Slave Termi-
nal configura-
tion informa-
tion
Unit config-
uration in-
formation
Perform the following operation with the
Controller set to the NJ/NX-series CPU
Unit.
Transfer the EtherCAT network configura-
tion information and the Slave Terminal
configuration information from the Syn-
chronization Window.
Transferred on the
Slave Terminal Tab
Page.
Communi-
cations
Coupler
Unit
I/O alloca-
tion infor-
mation
Communi-
cations
Coupler
Unit and
Safety CPU
Unit
Safety appli-
cation data
Unvalidated
safety appli-
cation data
The safety application data is transferred automatically when you
change to DEBUG mode from the Safety CPU Unit Setup and
Programming View.
Safety CPU
Unit
Validated
safety appli-
cation data
In DEBUG mode, execute
Safety Validation
from the Safety CPU
Unit Setup and Programming View. This will cause the safety ap-
plication data to be saved to the non-volatile memory.
Perform the following operation with the
Controller set to the NJ/NX-series CPU
Unit.
Transfer the EtherCAT network configura-
tion information and the Slave Terminal
configuration information from the Syn-
chronization Window.
Transferred on the
Slave Terminal Tab
Page.
*1.
This is required only when you use an EtherCAT network.
*2.
In the following cases, only the Slave Terminal is restarted after the data is transferred.
7 Checking Operation and Actual Operation
7 - 5
NX-series Safety Control Unit User's Manual (Z930)
7-1 Procedures before Operation and T
ransferring the Required Data
7
7-1-2
Data That Y
ou Must T
ransfer before Operation and Data T
ransfer Procedures
Содержание NX-SIH400
Страница 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Страница 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Страница 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Страница 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Страница 378: ...7 Checking Operation and Actual Operation 7 72 NX series Safety Control Unit User s Manual Z930 ...
Страница 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Страница 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Страница 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Страница 550: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 38 NX series Safety Control Unit User s Manual Z930 ...
Страница 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 558: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 46 NX series Safety Control Unit User s Manual Z930 ...
Страница 564: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 52 NX series Safety Control Unit User s Manual Z930 ...
Страница 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Страница 625: ......