80300000 hex
[NX-SL3
£££
]
Safety Proc-
ess Data
Communica-
tions Time-
out
A communications
timeout occurred in
safety process data
communications with
the Safety Control
Unit.
•
A setting is not correct. The
setting of the safety task peri-
od is too short.
•
There is excessive noise.
•
The Safety CPU Unit or safety
slave entered a status where it
could not continue safety proc-
ess data communications.
•
The process data communica-
tions were not performed cor-
rectly because an error or sta-
tus change occurred in the NX
bus master to which the Unit is
connected.
¡
80300001 hex
[NX-SL5
£££
]
FSoE Mas-
ter Connec-
tion Timeout
A communication
timeout occurred in
FSoE communica-
tions with the FSoE
slave.
•
A setting is not correct. The
setting of the safety task peri-
od is too short.
•
There is excessive noise.
•
The Safety CPU Unit or FSoE
slave entered a state where it
could not continue FSoE com-
munications.
•
The process data communica-
tions were not performed cor-
rectly because an error or sta-
tus change occurred in the NX
bus master to which the Unit is
connected.
¡
80310000 hex
[NX-SL5
£££
]
CIP Safety
Originator
Connection
Not Estab-
lished Error
CIP safety originator
connection was not
established.
•
The target node is different.
•
The target node is not config-
ured.
•
The target node status is inva-
lid.
¡
80320000 hex
[NX-SL5
£££
]
CIP Safety
Originator
Connection
Timeout
A timeout occurred in
CIP safety originator
connection.
•
The communications cable is
disconnected or broken.
•
The target node entered a
state where it could not accept
the connection.
•
The timeout value in the com-
munications setup is too small.
•
There is excessive noise.
¡
80330000 hex
[NX-SL5
£££
]
CIP Safety
Target Does
Not Exist
The target node does
not exist.
•
The communications cable is
disconnected or broken.
•
The target node entered a
state where it could not accept
the connection.
•
The timeout value in the com-
munications setup is too small.
•
There is excessive noise.
¡
12 Troubleshooting
12 - 20
NX-series Safety Control Unit User's Manual (Z930)
Содержание NX-SIH400
Страница 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Страница 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Страница 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Страница 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Страница 378: ...7 Checking Operation and Actual Operation 7 72 NX series Safety Control Unit User s Manual Z930 ...
Страница 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Страница 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Страница 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Страница 550: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 38 NX series Safety Control Unit User s Manual Z930 ...
Страница 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 558: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 46 NX series Safety Control Unit User s Manual Z930 ...
Страница 564: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 52 NX series Safety Control Unit User s Manual Z930 ...
Страница 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Страница 625: ......