Event name
Division by Zero
Event code
55000000 hex
Meaning
Division by zero was detected.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Source details
NX Unit
Detection tim-
ing
In DEBUG
mode (RUN) or
RUN mode
Error attrib-
utes
Level
Minor fault
Recovery
Automatic re-
covery
Log category
System
Effects
User program
Continues.
Operation
The CPU Unit executes NX bus communications
but execution of the user program stops. (All I/O
data will remain at 0.)
System-de-
fined varia-
bles
Variable
Data type
Name
None
None
None
Cause and
correction
Assumed cause
Correction
Prevention
The divisor is zero.
Correct the program so that the
divisor is not 0.
Perform the following corrections
according to the operating mode
of the Safety CPU Unit.
•
RUN mode: Change to PRO-
GRAM mode and transfer the
corrected user program.
•
DEBUG mode (RUN): Change
to PROGRAM mode and
transfer the corrected user
program.
Program operation considering
the corrections that are given on
the left.
Attached in-
formation
None
Precautions/
Remarks
The CPU Unit executes NX bus communications but execution of the user program stops. (All I/O data
will remain at 0.)
12 Troubleshooting
12 - 53
NX-series Safety Control Unit User's Manual (Z930)
12-3 Checking for Errors with the Sysmac Studio
12
12-3-4 Error Descriptions
Содержание NX-SIH400
Страница 4: ...Introduction 2 NX series Safety Control Unit User s Manual Z930 ...
Страница 46: ...Revision History 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 108: ...2 Specifications 2 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 132: ...3 Installation and Wiring 3 24 NX series Safety Control Unit User s Manual Z930 ...
Страница 148: ...4 Safety Control Unit Operation 4 16 NX series Safety Control Unit User s Manual Z930 ...
Страница 216: ...5 System Configuration and Setup 5 44 NX series Safety Control Unit User s Manual Z930 ...
Страница 306: ...6 Programming 6 90 NX series Safety Control Unit User s Manual Z930 ...
Страница 378: ...7 Checking Operation and Actual Operation 7 72 NX series Safety Control Unit User s Manual Z930 ...
Страница 390: ...8 Calculating Safety Reaction Times 8 12 NX series Safety Control Unit User s Manual Z930 ...
Страница 412: ...11 Safety Data Logging 11 10 NX series Safety Control Unit User s Manual Z930 ...
Страница 504: ...12 Troubleshooting 12 92 NX series Safety Control Unit User s Manual Z930 ...
Страница 550: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 38 NX series Safety Control Unit User s Manual Z930 ...
Страница 554: ...l I O Map Settings Appendices A 42 NX series Safety Control Unit User s Manual Z930 ...
Страница 558: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 46 NX series Safety Control Unit User s Manual Z930 ...
Страница 564: ...l Safety I O Terminal Settings l I O Map Settings Appendices A 52 NX series Safety Control Unit User s Manual Z930 ...
Страница 623: ...I Index I 1 NX series Safety Control Unit User s Manual Z930 I ...
Страница 625: ......