Section 2 NS Series Functions
2-4 System Memory
2-32
NS Series Programming Manual
Save Error Log ($SB43)
$SB43 saves error log data. When $SB43 is turned ON, the error log data is saved to the Memory
Card as a CSV file. Once the data has been saved, the system automatically turns OFF $SB43.
The data is output to a file called MacroErr.csv in the Memory Card \log\ directory. The file names are
fixed and files previously output to the Memory Card will be overwritten.
If there is no accumulated data log, only the title line will be output. ($SB43 will turn OFF and $SB47
will not turn ON.)
If an error occurs during the save operation (e.g., the Memory Card is not in place, there is insufficient
free disk space, or the Memory Card is damaged), $SB43 will turn OFF and $SB47 will turn ON.
No error message will appear on the screen, however, when an error occurs.
If $SB42 and $SB43 turn ON simultaneously, initialization will be executed first. For this reason, no
MacroErr.CSV file will be created.
R
R
R
e
e
e
f
f
f
e
e
e
r
r
r
e
e
e
n
n
n
c
c
c
e
e
e
♦
Log data can be output in multibyte code or Unicode. This enables outputting data displayed in
other languages as log data. For details on using other languages, refer to
Reference –
Multi-language Display
in the
CX-Designer Online Help
.
Macro Error Dialog Control ($SB45)
$SB45 changes the processing for macro errors. If $SB45 turns ON, no error dialog box is displayed
when a macro error occurs but the execution of macro processing is stopped. If $SB45 is turned OFF,
an error dialog box will be displayed and macro execution will be stopped.
N
N
N
o
o
o
t
t
t
e
e
e
♦
When a macro error occurs, processing of the macro where the error occurred will be interrupted
regardless of whether or not $SB45 is ON or OFF, but other macro processing will continue.
Notification Macro Error ($SB46)
$SB46 turns ON when a macro execution error occurs.
$SB46 will remain ON until turned OFF from the host, using a functional object, or other method.
If a macro error occurs when values are being changed, the macro error notification is executed after
the Macro Error Dialog Box is closed by pressing the OK Button. Macro error notification will be exe-
cuted immediately after any other macro error occurs.
Logging Process Error Flag ($SB47)
$SB47 turns ON if an error occurs during alarm, data log, operation history, error log processing, or
video capture.
$SB47 will remain ON until turned OFF from the host, using a functional object, or other method.
Memory Free Space Check ($SB48)
$SB48 turns ON when the free space on the Memory Card mounted to the PT drops below a specified
size when saving data to the Memory Card.
The amount of free space that will trigger the warning is set using
Free Space
under CX-Designer
System Setting – Initial.
The default is 1,024 bytes.
Stop Memory Card ($SB49)
$SB49 is turned ON to remove the Memory Card. When $SB49 is turned ON, the Memory Card power
Содержание NS -
Страница 2: ......
Страница 12: ...Contents vi NS Series Programming Manual...
Страница 46: ...Section 1 Overview 1 5 Procedure before Operation 1 33 NS Series Programming Manual...
Страница 590: ...Section 3 Using PTs 3 12 Function Key Settings NS15 Only 3 35 NS Series Programming Manual...
Страница 604: ...Section 4 Using Functions 4 1 Application 4 13 NS Series Programming Manual...
Страница 640: ...Section 5 Troubleshooting and Maintenance 5 2 Error Messages 5 35 NS Series Programming Manual...
Страница 680: ...Appendices Appendix 6 Additional NS Series Functions A 39 NS Series Programming Manual...
Страница 682: ......
Страница 683: ......