Section 5 Troubleshooting and Maintenance
5-2 Error Messages
5-33
NS Series Programming Manual
Message Cause
Possible countermeasure
Time-out error occurred while
writing due to the following:
Disconnection of the connecting
cable
Stopped host_- Incorrect
time-out period
Allocation Host: XXXX
Do you want to retry?
NS5:
Time-out error occurred while
writing to the System Memory
Area.
Allocation Host: XXXX
Do you want to retry?
The communications
cable is not properly
connected. The host
communications
service has stopped.
The timeout monitoring
time is too short.
Check the cable connection and conduct a
continuity test. Replace the cable if there is a
cable error, or rewire the cable if necessary.
Communication error
detected while writing by the
following case:
Corrupted data by noise
Transmit error by the host
Allocation Host: XXXX
Do you want to retry?
NS5:
Communication error detected
while writing to the System
Memory Area
Allocation Host: XXXX
Do you want to retry?
Data corrupted by
noise
Invalid host communi-
cations command
Check the cable connection and conduct a
continuity test. Replace the cable if there is a
cable error, or rewire the cable if necessary.
Communication error
detected while writing by the
following case:
Corrupted data by noise
Transmit error by the host
Allocation Host: XXXX
Do you want to retry?
NS5:
Communication error
detected while writing to the
System Memory Area.
Allocation Host: XXXX
Do you want to retry?
Data corrupted by
noise
Invalid host communi-
cations command
Check the cable connection and conduct a
continuity test. Replace the cable if there is a
cable error, or rewire the cable if necessary.
Addressing error exists in the
screen, alarm, data log, or
macro. Correct address setting
by the CX-Designer.
Screen No.: XXXX
Allocation Host: XXXX
Allocation Address: XXXX
NS5:
Addressing error exists in the
screen, alarm, data log or
macro.
Screen No.: XXXX
Allocation Host: XXXX
Allocation Address: XXXX
The storage type of the
number set for a func-
tional object does not
match the data type of
the tag.
Settings are made to
monitor data that ex-
ceeds the maximum
number of elements for
an array variable.
Change the settings using the CX-Designer.
Alternatively, change the host tag settings.
Содержание NS -
Страница 2: ......
Страница 12: ...Contents vi NS Series Programming Manual...
Страница 46: ...Section 1 Overview 1 5 Procedure before Operation 1 33 NS Series Programming Manual...
Страница 590: ...Section 3 Using PTs 3 12 Function Key Settings NS15 Only 3 35 NS Series Programming Manual...
Страница 604: ...Section 4 Using Functions 4 1 Application 4 13 NS Series Programming Manual...
Страница 640: ...Section 5 Troubleshooting and Maintenance 5 2 Error Messages 5 35 NS Series Programming Manual...
Страница 680: ...Appendices Appendix 6 Additional NS Series Functions A 39 NS Series Programming Manual...
Страница 682: ......
Страница 683: ......