H5CR
H5CR
176
Ratings
Model
H5CR-L (Basic type)
H5CR-B (Standard type)
H5CR-S (Short body type)
Rated supply voltage
100 to 240 VAC (50/60 Hz)
24 VAC (50/60 Hz)
12 to 24 VDC (permissible ripple:
20% max.)
100 to 240 VAC (50/60 Hz)
24 VAC (50/60 Hz)
12 to 24 VDC (permissible ripple:
20% max.)
Operating voltage range
85% to 110% of rated voltage
Power consumption
Approx. 3 VA at 50 Hz, 240 VAC;
approx. 1 W at 24 VDC
Approx. 5 VA at 50 Hz, 240 VAC
Approx. 2 W at 24 VDC
Reset and control signals
Min. pulse width 1 ms/20ms selectable
Gate
---
Min. pulse width: Approx. 20 ms
Key protect
---
Response time: 1 s
One-shot time
0.1 to 20 s (select from 7 kinds) or hold
Power reset (except A-3,
b-1, and F mode)
Min. power opening time: 0.5 s
Signal, reset, gate inputs
No-voltage input
ON impedance:
1 k
$
max. (Approx. 2 mA when 0
$
)
ON residual voltage: 2 V max.
OFF impedance:
100 k
$
min.a
Key protect input
---
No-voltage input
ON impedance:
1 k
$
max. (Approx. 2 mA when 0
$
)
ON residual voltage: 1 V max.
OFF impedance:
100 k
$
min.
Control outputs
Contacts: 5 A at 250 VAC, resistance load (cos
%
= 1)
Transistor output: Open collector 100mA at 30 VDC max. residual voltage 2 V max. (Approx. 1 V)
Ambient temperature
-10
"
C to 55
"
C (with no icing)
Storage temperature
-25
"
C to 65
"
C (with no icing)
Ambient humidity
35% to 85%
Case
Light gray
Characteristics
Repeat accuracy (including temperature and
voltage effects)
Power start:
!
0.01%
!
0.05 s max.
Control signal start:
!
0.005%
!
0.03 s max. *(rate for set value)
Insulation resistance
100 M
$
min. (at 500 VDC) (between current-carrying terminal and exposed
non-current-carrying metal parts, and between non-continuous contacts)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminal and
exposed non-current-carrying metal parts) for 100 to 240 VAC type
1,000 VAC for 24VAC/12 to 24 VDC type
Surge voltage
3 kV (between power terminals) for 100 to 240 VAC type, 1 kV for 24 VAC/12 to
24 VDC type
4.5 kV (between current-carrying terminal and exposed non-current-carrying
metal parts) for 100 to 240 VAC type, 1.5 kV for 24 VAC/12 to 24 VDC type
Noise immunity
!
2 kV (between power terminals)(
!
480 V for 12 to 24 VDC) and
!
600 V
(between input terminals), square-wave noise by noise simulator (pulse width:
100 ns/1
&
s, 1-ns rise)
Static immunity
Malfunction: 8 kV; destruction: 15 kV
Vibration
Destruction
10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction
10 to 55 Hz with 0.5-mm single amplitude each in three directions
Shock
Destruction
294 m/s
2
(30G) each in three directions
Malfunction
98 m/s
2
(10G) each in three directions
Life expectancy
Mechanical
10 million operations min.
Electrical
100,000 operations min. (5 A at 250 VAC in load resistance)
Weight
H5CR-L: Approx. 105 g, H5CR-B: Approx. 160 g, H5CR-S: Approx: 120 g