Selection Guide
3
Classification
Solid-state Timer
Model
H3DR-F
H3DR-G
H3DR-H
Features
DIN 22.5-mm Solid-state Twin
Timers
DIN 22.5-mm Solid-state
Star-delta Timers
DIN 22.5-mm Solid-state Power
OFF-delay Timers
Appearance and dimensions
22.5
75
100
22.5
75
100
22.5
75
100
Time range (60 Hz)
0.1 s to 12 h
1 to 120 s
0.1 to 120 s
Supply voltage
100 to 240 VAC (50/60 Hz),
48 VAC (50/60 Hz),
24 VAC/VDC (50/60 Hz),
12 VDC
100 to 240 VAC (50/60 Hz),
48 VAC (50/60 Hz),
24 VAC/VDC (50/60 Hz)
100/110/120 VAC (50/60 Hz),
200/220/240 VAC (50/60 Hz),
24 VAC/VDC (50/60 Hz),
48 VAC/VDC (50/60 Hz)
Power consumption
8.2 VA, 1.7 VA, 1.3 VA/0.6 W,
0.4 W
11 VA, 1.2 VA, 0.9 VA/0.45 W
0.5 VA, 0.8 VA, 0.17 VA/0.13 W,
0.36 VA/0.34 W
Accuracy of operating time
!
1% max.
!
1% max.
!
1% max.
Control output
5 A at 250 VAC
5 A at 250 VAC
5 A at 250 VAC
Contact
fi
ti
Time-limit
SPDT
SPST-NO
SPDT
configuration
Instantaneous
---
---
---
Life expectancy
20 x 10
6
operations
20 x 10
6
operations
10 x 10
6
operations
EMC
Conforms to EN50081-2,
prEN50082-2
Conforms to EN50081-2,
prEN50082-2
Conforms to EN50081-2,
prEN50082-2
Approved standards
UL, CSA, conforms to VDE
UL, CSA, conforms to VDE
UL, CSA, conforms to VDE
Page
90
95
100
Classification
Solid-state Timer
Model
H3CA
H3Y
H3M
Features
DIN-sized (48 x 48 mm, 45 x
75 mm) Timer with digital
setting and LCD display -
multifunctions
Subminiature Timer
incorporating exclusive IC ideal
for sequence control
Solid-state Timer with variable
time ranges
Appearance and dimensions
48
48
89
28
21.5
50
40
67.1
Time range (60 Hz)
0.1 s to 9.990 h
0.5 s to 3 h
0.05 to 30 h
Supply voltage
24 to 240 VAC (50/60 Hz),
12 to 240 VDC
100, 110, 120, 200, 220, or
240 VAC (50/60 Hz),
12, 24, 48, 100, or 110 VDC
100/110/120, 200/220/
240 VAC (50/60 Hz),
12, 24, 48, 100, or 110 VDC
Power consumption
2 to 10 VA, 1 to 2 W
2 VA, 2 W
5 VA/2 W, 2 W
Accuracy of operating time
!
0.3%
!
0.05 s
!
2%
!
1%
Control output
3 A at 250 VAC
5 A at 250 VAC
5 A at 250 VAC
Contact
configuration
Time-limit
SPDT
SPDT, DPDT
DPDT, 3PDT,
4PDT
Solid-state
DPDT
SPDT
co
gu at o
Instantaneous
---
SPDT
---
---
SPDT
Life expectancy
10 x 10
6
operations
10 x 10
6
operations
20 x 10
6
operations
EMC
---
Conforms to EN50081-2,
prEN50082-2 (except IEC801-4)
---
Approved standards
UL, CSA, SEV
UL, CSA
UL, CSA
Page
109
123
132